Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1998-07-01 → 1998-07-31 |
| MCL | Health-based | Resolved | 1998-07-01 → 1998-07-31 |
| Other | Monitoring | Archived | 1988-08-01 → 1988-08-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 10 µg/L 100% of the EPA limit 10 µg/L
worst single sample: 15 µg/L | 492/494 | SYR4 | 2012–2019 |
| Lead | 0.0060 mg/L 40% of the EPA limit 0.0150 mg/L | 38/38 | LCR | 2025 |
| Fluoride | 183 µg/L 4.6% of the EPA limit 4000 µg/L
worst single sample: 190 µg/L | 15/15 | SYR4 | 2012–2018 |
| Barium | 200 µg/L 10% of the EPA limit 2000 µg/L | 12/16 | SYR4 | 2012–2018 |
| TTHM | 25.88 µg/L 32% of the EPA limit 80 µg/L
worst single sample: 30 µg/L | 9/9 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.355 µg/L No EPA limit set
worst single sample: 6.6 µg/L | 8/9 | SYR4 | 2012–2019 |
| Bromoform | 2.4 µg/L No EPA limit set | 8/9 | SYR4 | 2012–2019 |
| Chloroform | 4.19 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 8/9 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.9 µg/L No EPA limit set | 8/9 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 5.715 µg/L 9.5% of the EPA limit 60 µg/L
worst single sample: 6.1 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.98 µg/L No EPA limit set
worst single sample: 3.1 µg/L | 7/7 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2.82 µg/L No EPA limit set
worst single sample: 3 µg/L | 7/7 | SYR4 | 2012–2019 |
| Nitrate | 150 µg/L 1.5% of the EPA limit 10000 µg/L | 4/88 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.285 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 2/7 | SYR4 | 2012–2019 |
| Lithium | 13.2 µg/L No EPA limit set | 2/4 | UCMR-5 | 2023 |
96 contaminants tested, none detected
Utility contact
Frequently asked questions about California-American Larkfield (Puc)
Is California-American Larkfield (Puc) tap water safe to drink?
EPA monitoring detected 15 contaminants in California-American Larkfield (Puc)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in California-American Larkfield (Puc)'s water?
EPA monitoring detected Arsenic, Lead, Fluoride, Barium, TTHM, and others. The full list with the level and data source for each is above.
How many people does California-American Larkfield (Puc) serve?
California-American Larkfield (Puc) reports serving 7,913 people in California, per its EPA record.
Has California-American Larkfield (Puc) had any water quality violations?
The EPA has 3 violations on file for California-American Larkfield (Puc), of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.