Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| MCL | Health-based | Resolved | 1991-10-01 → 1991-12-31 |
| MCL | Health-based | Resolved | 1991-10-01 → 1991-12-31 |
| MCL | Health-based | Resolved | 1990-07-01 → 1990-09-30 |
| MCL | Health-based | Resolved | 1990-07-01 → 1990-09-30 |
| MR | Monitoring | Resolved | 1993-05-01 → 1993-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 12.1765 µg/L No EPA limit set
worst single sample: 13.89 µg/L | 32/32 | SYR4 | 2019 |
| Chloroform | 55.604 µg/L No EPA limit set
worst single sample: 73.06 µg/L | 32/32 | SYR4 | 2019 |
| Dibromochloromethane | 4.9995 µg/L No EPA limit set
worst single sample: 5.15 µg/L | 32/32 | SYR4 | 2019 |
| Dichloroacetic Acid | 11.855 µg/L No EPA limit set
worst single sample: 18.3 µg/L | 32/32 | SYR4 | 2019 |
| TTHM | 71.501 µg/L 89% of the EPA limit 80 µg/L
worst single sample: 91.42 µg/L | 32/32 | SYR4 | 2019 |
| Total Haloacetic Acids (HAA5) | 22.09 µg/L 37% of the EPA limit 60 µg/L
worst single sample: 31.1 µg/L | 32/32 | SYR4 | 2019 |
| Trichloroacetic Acid | 8.705 µg/L No EPA limit set
worst single sample: 11.3 µg/L | 32/32 | SYR4 | 2019 |
| Fluoride | 866.5 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 960 µg/L | 30/45 | SYR4 | 2012–2019 |
| Arsenic | 4.57 µg/L 46% of the EPA limit 10 µg/L
worst single sample: 4.68 µg/L | 27/38 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 27/27 | LCR | 2024 |
| Nitrate | 1532.28 µg/L 15% of the EPA limit 10000 µg/L | 12/102 | SYR4 | 2012–2019 |
| Lead | 47.8 µg/L 319% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 83 µg/L | 11/41 | SYR4 | 2012–2019 |
| Combined Uranium | 2.67008 µg/L 8.9% of the EPA limit 30 µg/L
worst single sample: 2.831 µg/L | 9/23 | SYR4 | 2012–2019 |
| Chromium | 92.115 µg/L 92% of the EPA limit 100 µg/L
worst single sample: 103 µg/L | 8/40 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.45 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 6/32 | SYR4 | 2019 |
| Bromate | 2.66 µg/L 27% of the EPA limit 10 µg/L
worst single sample: 2.7 µg/L | 5/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.99 µg/L No EPA limit set
worst single sample: 3 µg/L | 3/32 | SYR4 | 2019 |
| Cadmium | 2.245 µg/L 45% of the EPA limit 5 µg/L
worst single sample: 2.3 µg/L | 2/38 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 985650 µg/L 9857% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 1000000 µg/L | 2/38 | SYR4 | 2012–2019 |
| Copper | 55 µg/L 4.2% of the EPA limit 1300 µg/L | 1/42 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 3.8 µg/L 63% of the EPA limit 6 µg/L | 1/18 | SYR4 | 2012–2019 |
| Trichloroethylene | 0.9700 µg/L 19% of the EPA limit 5 µg/L | 1/36 | SYR4 | 2012–2019 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Vallejo
Is City of Vallejo tap water safe to drink?
EPA monitoring detected 22 contaminants in City of Vallejo's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Vallejo's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does City of Vallejo serve?
City of Vallejo reports serving 121,420 people in California, per its EPA record.
Has City of Vallejo had any water quality violations?
The EPA has 11 violations on file for City of Vallejo, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.