← California

Tap water quality report

Purissima Hills Water District

EPA monitoring tested this supplier for 42 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

42
contaminants tested
11
detected
6,245
people served
12
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Santa Clara

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
14
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1999-11-01 → 1999-11-30
MCL Health-based Resolved 1999-11-01 → 1999-11-30
MCL Health-based Resolved 1999-11-01 → 1999-11-30
MCL Health-based Resolved 1999-11-01 → 1999-11-30
TT Health-based Resolved 1998-08-01 → 1998-08-31
TT Health-based Resolved 1998-08-01 → 1998-08-31
TT Health-based Resolved 1995-03-01 → 1995-03-31
TT Health-based Resolved 1995-03-01 → 1995-03-31
TT Health-based Resolved 1992-03-01 → 1992-03-31
TT Health-based Resolved 1992-03-01 → 1992-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Dichloroacetic Acid
30.9 µg/L
No EPA limit set
worst single sample: 51.2 µg/L
64/64 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
53.875 µg/L 90%
of the EPA limit 60 µg/L
worst single sample: 77.8 µg/L
64/64 SYR4 2012–2019
Trichloroacetic Acid
24.905 µg/L
No EPA limit set
worst single sample: 33.8 µg/L
64/64 SYR4 2012–2019
Chloroform
61.334 µg/L
No EPA limit set
worst single sample: 65.55 µg/L
63/64 SYR4 2012–2019
TTHM
62.686 µg/L 78%
of the EPA limit 80 µg/L
worst single sample: 67.73 µg/L
63/64 SYR4 2012–2019
Bromodichloromethane
3.905 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
46/64 SYR4 2012–2019
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
40/40 LCR 2023
Monochloroacetic Acid
3.59 µg/L
No EPA limit set
worst single sample: 3.7 µg/L
3/64 SYR4 2012–2019
Dibromochloromethane
2.472 µg/L
No EPA limit set
worst single sample: 2.53 µg/L
2/64 SYR4 2012–2019
Bromoform
3.22 µg/L
No EPA limit set
1/64 SYR4 2012–2019
Dibromoacetic Acid
1.3 µg/L
No EPA limit set
1/64 SYR4 2012–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
WALTER, ERIK
Phone
650-948-1217
Email
[email protected]

Frequently asked questions about Purissima Hills Water District

Is Purissima Hills Water District tap water safe to drink?

EPA monitoring detected 11 contaminants in Purissima Hills Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Purissima Hills Water District's water?

EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Purissima Hills Water District serve?

Purissima Hills Water District reports serving 6,245 people in California, per its EPA record.

Has Purissima Hills Water District had any water quality violations?

The EPA has 14 violations on file for Purissima Hills Water District, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.