Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2015-03-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-03-01 → 2015-03-31 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| TT | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| MCL | Health-based | Resolved | 1992-10-01 → 1992-10-31 |
| Other | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
| Other | Monitoring | Resolved | 2006-04-01 → 2006-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 58.28 µg/L No EPA limit set
worst single sample: 101.1 µg/L | 317/317 | SYR4 | 2012–2019 |
| TTHM | 71.02 µg/L 89% of the EPA limit 80 µg/L
worst single sample: 124.2 µg/L | 317/317 | SYR4 | 2012–2019 |
| Bromodichloromethane | 15.931 µg/L No EPA limit set
worst single sample: 19.94 µg/L | 302/317 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32 µg/L No EPA limit set
worst single sample: 38 µg/L | 298/298 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 54 µg/L 90% of the EPA limit 60 µg/L
worst single sample: 69 µg/L | 298/298 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 23 µg/L No EPA limit set
worst single sample: 33 µg/L | 298/298 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.61 µg/L No EPA limit set
worst single sample: 9.75 µg/L | 117/317 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.2 µg/L No EPA limit set
worst single sample: 5.3 µg/L | 74/298 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 42/42 | LCR | 2024 |
| Fluoride | 377.5 µg/L 9.4% of the EPA limit 4000 µg/L
worst single sample: 610 µg/L | 16/16 | SYR4 | 2012–2019 |
| Antimony, Total | 0.2215 µg/L 3.7% of the EPA limit 6 µg/L
worst single sample: 0.2410 µg/L | 14/49 | SYR4 | 2012–2019 |
| Arsenic | 1.73185 µg/L 17% of the EPA limit 10 µg/L
worst single sample: 1.739 µg/L | 14/54 | SYR4 | 2012–2019 |
| Copper | 27.984 µg/L 2.2% of the EPA limit 1300 µg/L
worst single sample: 32.051 µg/L | 14/52 | SYR4 | 2012–2019 |
| Chromium | 7.2165 µg/L 7.2% of the EPA limit 100 µg/L
worst single sample: 14.347 µg/L | 14/53 | SYR4 | 2012–2019 |
| Lead | 0.4694 µg/L 3.1% of the EPA limit 15 µg/L
worst single sample: 0.5780 µg/L | 14/52 | SYR4 | 2012–2019 |
| Cadmium | 0.0280 µg/L 0.6% of the EPA limit 5 µg/L
worst single sample: 0.0380 µg/L | 11/51 | SYR4 | 2012–2019 |
| Combined Uranium | 1.03332 µg/L 3.4% of the EPA limit 30 µg/L
worst single sample: 1.04747 µg/L | 11/32 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 6.2 µg/L No EPA limit set | 9/298 | SYR4 | 2012–2019 |
| Selenium | 3.8644 µg/L 7.7% of the EPA limit 50 µg/L
worst single sample: 4.084 µg/L | 9/45 | SYR4 | 2012–2019 |
| Bromoform | 33.732 µg/L No EPA limit set
worst single sample: 51.19 µg/L | 8/317 | SYR4 | 2012–2019 |
| Barium | 107 µg/L 5.4% of the EPA limit 2000 µg/L
worst single sample: 110 µg/L | 7/32 | SYR4 | 2012–2019 |
| Beryllium, Total | 0.0118 µg/L 0.3% of the EPA limit 4 µg/L
worst single sample: 0.0130 µg/L | 5/44 | SYR4 | 2012–2019 |
| Mercury | 0.0195 µg/L 1% of the EPA limit 2 µg/L
worst single sample: 0.0210 µg/L | 4/20 | SYR4 | 2012–2019 |
| Nitrate | 91.756 µg/L 0.9% of the EPA limit 10000 µg/L | 4/46 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.3 µg/L No EPA limit set | 1/298 | SYR4 | 2012–2019 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about California Water Service - Bear Gulch
Is California Water Service - Bear Gulch tap water safe to drink?
EPA monitoring detected 25 contaminants in California Water Service - Bear Gulch's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in California Water Service - Bear Gulch's water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does California Water Service - Bear Gulch serve?
California Water Service - Bear Gulch reports serving 61,431 people in California, per its EPA record.
Has California Water Service - Bear Gulch had any water quality violations?
The EPA has 7 violations on file for California Water Service - Bear Gulch, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.