← California

Tap water quality report

San Gabriel Valley Wc - Fontana

EPA monitoring tested this supplier for 111 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

111
contaminants tested
21
detected
237,700
people served
0
health-based violations
Water source
Surface water
Ownership
Private
Counties served
San Bernardino

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
7800 µg/L 78%
of the EPA limit 10000 µg/L
worst single sample: 14464 µg/L
4826/4846 SYR4 2012–2019
Tetrachloroethylene
4.9 µg/L 98%
of the EPA limit 5 µg/L
worst single sample: 7.6 µg/L
540/1592 SYR4 2012–2019
Fluoride
480 µg/L 12%
of the EPA limit 4000 µg/L
worst single sample: 660 µg/L
231/236 SYR4 2012–2019
TTHM
61.3 µg/L 77%
of the EPA limit 80 µg/L
worst single sample: 76 µg/L
188/284 SYR4 2012–2019
Dibromochloromethane
25 µg/L
No EPA limit set
worst single sample: 29 µg/L
157/283 SYR4 2012–2019
Bromodichloromethane
18 µg/L
No EPA limit set
worst single sample: 23 µg/L
146/282 SYR4 2012–2019
Chloroform
24 µg/L
No EPA limit set
worst single sample: 36 µg/L
135/282 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
21 µg/L 35%
of the EPA limit 60 µg/L
worst single sample: 30 µg/L
126/232 SYR4 2012–2019
Bromoform
14.8 µg/L
No EPA limit set
worst single sample: 25 µg/L
123/283 SYR4 2012–2019
Nitrate-Nitrite
874000 µg/L 8740%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 1000000 µg/L
114/120 SYR4 2012–2019
Dibromoacetic Acid
6.8 µg/L
No EPA limit set
worst single sample: 7.7 µg/L
107/232 SYR4 2012–2019
Dichloroacetic Acid
9.7 µg/L
No EPA limit set
worst single sample: 14 µg/L
101/232 SYR4 2012–2019
Trichloroacetic Acid
11.05 µg/L
No EPA limit set
worst single sample: 14 µg/L
80/232 SYR4 2012–2019
Arsenic
6.01 µg/L 60%
of the EPA limit 10 µg/L
worst single sample: 6.2 µg/L
27/236 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
19/19 LCR 2024
Dichloromethane
10.92 µg/L 218%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 15 µg/L
7/252 SYR4 2012–2019
Combined Uranium
5.215 µg/L 17%
of the EPA limit 30 µg/L
5/5 SYR4 2013–2019
Monobromoacetic Acid
1.1 µg/L
No EPA limit set
4/232 SYR4 2012–2019
1,2-DIBROMO-3-CHLOROPROPANE
0.0129 µg/L 6.4%
of the EPA limit 0.2000 µg/L
worst single sample: 0.0130 µg/L
2/131 SYR4 2012–2019
Copper
216.5 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 220 µg/L
2/236 SYR4 2012–2019
Lead
19 µg/L 127%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
1/236 SYR4 2012–2019
90 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TARANGO, ERIC D.
Phone
909-201-7330
Email
[email protected]

Frequently asked questions about San Gabriel Valley Wc - Fontana

Is San Gabriel Valley Wc - Fontana tap water safe to drink?

EPA monitoring detected 21 contaminants in San Gabriel Valley Wc - Fontana's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in San Gabriel Valley Wc - Fontana's water?

EPA monitoring detected Nitrate, Tetrachloroethylene, Fluoride, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does San Gabriel Valley Wc - Fontana serve?

San Gabriel Valley Wc - Fontana reports serving 237,700 people in California, per its EPA record.

Has San Gabriel Valley Wc - Fontana had any water quality violations?

The EPA has no formal drinking-water violations on file for San Gabriel Valley Wc - Fontana.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.