Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1994-01-01 → 1994-01-31 |
| MCL | Health-based | Resolved | 1994-01-01 → 1994-01-31 |
| MCL | Health-based | Resolved | 1993-05-01 → 1993-06-30 |
| MCL | Health-based | Resolved | 1993-05-01 → 1993-06-30 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-07-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-07-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-07-31 |
| MR | Monitoring | Resolved | 2016-07-01 → 2016-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2260 µg/L 23% of the EPA limit 10000 µg/L
worst single sample: 2300 µg/L | 124/124 | SYR4 | 2012–2019 |
| Combined Uranium | 31.886 µg/L 106% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 34.27 µg/L | 33/33 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 25/25 | LCR | 2025 |
| Fluoride | 1105 µg/L 28% of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L | 20/20 | SYR4 | 2012–2019 |
| Arsenic | 6.34 µg/L 63% of the EPA limit 10 µg/L
worst single sample: 6.7 µg/L | 13/20 | SYR4 | 2012–2019 |
| Bromoform | 9 µg/L No EPA limit set
worst single sample: 12 µg/L | 11/12 | SYR4 | 2012–2019 |
| TTHM | 10.55 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 13.3 µg/L | 11/12 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 2180 µg/L 22% of the EPA limit 10000 µg/L
worst single sample: 2300 µg/L | 9/9 | SYR4 | 2017–2019 |
| Dibromoacetic Acid | 1.18 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 3/12 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.98 µg/L No EPA limit set
worst single sample: 2 µg/L | 3/12 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 1.18 µg/L 2% of the EPA limit 60 µg/L
worst single sample: 1.2 µg/L | 3/12 | SYR4 | 2012–2019 |
70 contaminants tested, none detected
Utility contact
Frequently asked questions about Bighorn - Desert View Water Agency
Is Bighorn - Desert View Water Agency tap water safe to drink?
EPA monitoring detected 11 contaminants in Bighorn - Desert View Water Agency's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bighorn - Desert View Water Agency's water?
EPA monitoring detected Nitrate, Combined Uranium, Lead, Fluoride, Arsenic, and others. The full list with the level and data source for each is above.
How many people does Bighorn - Desert View Water Agency serve?
Bighorn - Desert View Water Agency reports serving 3,916 people in California, per its EPA record.
Has Bighorn - Desert View Water Agency had any water quality violations?
The EPA has 14 violations on file for Bighorn - Desert View Water Agency, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.