Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1996-10-01 → 1997-09-30 |
| MCL | Health-based | Resolved | 1996-10-01 → 1997-09-30 |
| MCL | Health-based | Resolved | 1996-01-01 → 1996-01-31 |
| MCL | Health-based | Resolved | 1996-01-01 → 1996-01-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-07-01 → 1995-07-31 |
| MCL | Health-based | Resolved | 1995-06-01 → 1995-06-30 |
| MCL | Health-based | Resolved | 1995-06-01 → 1995-06-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFOA | 0.0046 µg/L | 1/9 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5198 µg/L 52% of the EPA limit 10000 µg/L
worst single sample: 5424 µg/L | 114/116 | SYR4 | 2012–2019 |
| Bromoform | 26.05 µg/L No EPA limit set
worst single sample: 40 µg/L | 100/105 | SYR4 | 2012–2019 |
| TTHM | 66.1 µg/L 83% of the EPA limit 80 µg/L
worst single sample: 110 µg/L | 100/105 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 12 µg/L No EPA limit set
worst single sample: 16 µg/L | 98/100 | SYR4 | 2013–2019 |
| Dibromochloromethane | 26.2 µg/L No EPA limit set
worst single sample: 48 µg/L | 97/105 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17 µg/L 28% of the EPA limit 60 µg/L
worst single sample: 26 µg/L | 86/100 | SYR4 | 2013–2019 |
| Bromodichloromethane | 13.25 µg/L No EPA limit set
worst single sample: 31 µg/L | 76/105 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 43/43 | LCR | 2023 |
| Dichloroacetic Acid | 4.245 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 20/100 | SYR4 | 2013–2019 |
| Chloroform | 6.4 µg/L No EPA limit set
worst single sample: 10 µg/L | 16/105 | SYR4 | 2012–2019 |
| Fluoride | 307.5 µg/L 7.7% of the EPA limit 4000 µg/L
worst single sample: 330 µg/L | 10/10 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 2.28 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 9/100 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 2.94 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 9/100 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 4280 µg/L 43% of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L | 5/5 | SYR4 | 2017 |
| Lithium | 23.5 µg/L No EPA limit set | 5/9 | UCMR-5 | 2025 |
| Chromium | 13.85 µg/L 14% of the EPA limit 100 µg/L
worst single sample: 14 µg/L | 4/10 | SYR4 | 2014–2017 |
| Arsenic | 3.43 µg/L 34% of the EPA limit 10 µg/L
worst single sample: 3.5 µg/L | 3/10 | SYR4 | 2014–2017 |
| Combined Uranium | 4.5892 µg/L 15% of the EPA limit 30 µg/L
worst single sample: 4.619 µg/L | 2/2 | SYR4 | 2014 |
| Selenium | 6.5 µg/L 13% of the EPA limit 50 µg/L | 1/10 | SYR4 | 2014–2017 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Sunnyslope County Water Dist
Is Sunnyslope County Water Dist tap water safe to drink?
EPA monitoring detected 20 contaminants in Sunnyslope County Water Dist's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Sunnyslope County Water Dist's water?
EPA monitoring detected Nitrate, Bromoform, TTHM, Dibromoacetic Acid, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Sunnyslope County Water Dist serve?
Sunnyslope County Water Dist reports serving 24,954 people in California, per its EPA record.
Has Sunnyslope County Water Dist had any water quality violations?
The EPA has 8 violations on file for Sunnyslope County Water Dist, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.