← California

Tap water quality report

San Juan Bautista, City of

EPA monitoring tested this supplier for 83 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

83
contaminants tested
17
detected
2,335
people served
14
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
San Benito

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
21
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
13847.5 µg/L 138%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 29280 µg/L
1466/1472 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
29/29 LCR 2025
Combined Uranium
8.35294 µg/L 28%
of the EPA limit 30 µg/L
worst single sample: 9.089 µg/L
14/16 SYR4 2014–2019
Bromoform
10.75 µg/L
No EPA limit set
worst single sample: 13 µg/L
10/17 SYR4 2014–2019
Dibromochloromethane
5.703 µg/L
No EPA limit set
worst single sample: 6 µg/L
10/17 SYR4 2014–2019
TTHM
17.931 µg/L 22%
of the EPA limit 80 µg/L
worst single sample: 21 µg/L
10/17 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
5.695 µg/L 9.5%
of the EPA limit 60 µg/L
worst single sample: 6.1 µg/L
10/13 SYR4 2014–2019
Dibromoacetic Acid
5.74 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
9/13 SYR4 2014–2019
Fluoride
1064 µg/L 27%
of the EPA limit 4000 µg/L
worst single sample: 1400 µg/L
9/9 SYR4 2014–2018
Nitrate-Nitrite
7320 µg/L 73%
of the EPA limit 10000 µg/L
worst single sample: 8100 µg/L
5/6 SYR4 2017–2018
Bromodichloromethane
3.131 µg/L
No EPA limit set
worst single sample: 3.32 µg/L
4/17 SYR4 2014–2019
Chloroform
1.4975 µg/L
No EPA limit set
worst single sample: 1.51 µg/L
2/17 SYR4 2014–2019
Trichloroacetic Acid
1.4 µg/L
No EPA limit set
2/13 SYR4 2014–2019
Arsenic
2.4 µg/L 24%
of the EPA limit 10 µg/L
1/9 SYR4 2014–2018
Barium
140 µg/L 7%
of the EPA limit 2000 µg/L
1/9 SYR4 2014–2018
Combined Radium (-226 And -228)
2 pCi/L 40%
of the EPA limit 5 pCi/L
1/1 SYR4 2018
Dichloroacetic Acid
1.5 µg/L
No EPA limit set
1/13 SYR4 2014–2019
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COLLICK, ASHLEY
Phone
831-623-4661
Email
[email protected]

Frequently asked questions about San Juan Bautista, City of

Is San Juan Bautista, City of tap water safe to drink?

EPA monitoring detected 17 contaminants in San Juan Bautista, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in San Juan Bautista, City of's water?

EPA monitoring detected Nitrate, Lead, Combined Uranium, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does San Juan Bautista, City of serve?

San Juan Bautista, City of reports serving 2,335 people in California, per its EPA record.

Has San Juan Bautista, City of had any water quality violations?

The EPA has 21 violations on file for San Juan Bautista, City of, of which 14 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.