Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 31/31 | LCR | 2023 |
| Nitrate | 1402.5 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1420 µg/L | 28/28 | SYR4 | 2012–2019 |
| Arsenic | 5.05 µg/L 51% of the EPA limit 10 µg/L
worst single sample: 6 µg/L | 20/20 | SYR4 | 2012–2019 |
| Bromoform | 35.01 µg/L No EPA limit set
worst single sample: 41.8 µg/L | 15/15 | SYR4 | 2012–2019 |
| Dibromochloromethane | 15.2 µg/L No EPA limit set
worst single sample: 20.4 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 9.935 µg/L No EPA limit set
worst single sample: 12.3 µg/L | 12/12 | SYR4 | 2014–2019 |
| TTHM | 52.98 µg/L 66% of the EPA limit 80 µg/L
worst single sample: 66.4 µg/L | 12/12 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 12.395 µg/L 21% of the EPA limit 60 µg/L
worst single sample: 15.2 µg/L | 12/12 | SYR4 | 2014–2019 |
| Bromodichloromethane | 3.6 µg/L No EPA limit set
worst single sample: 4.2 µg/L | 11/12 | SYR4 | 2014–2019 |
| Fluoride | 460 µg/L 12% of the EPA limit 4000 µg/L | 6/6 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.475 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 6/12 | SYR4 | 2014–2019 |
| Selenium | 11 µg/L 22% of the EPA limit 50 µg/L | 6/6 | SYR4 | 2012–2019 |
| Cadmium | 1 µg/L 20% of the EPA limit 5 µg/L | 2/6 | SYR4 | 2012–2019 |
| Combined Uranium | 4.59665 µg/L 15% of the EPA limit 30 µg/L
worst single sample: 4.619 µg/L | 2/2 | SYR4 | 2012–2014 |
| Dichloroacetic Acid | 1.39 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 2/12 | SYR4 | 2014–2019 |
| Nitrate-Nitrite | 1395 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1400 µg/L | 2/2 | SYR4 | 2016–2019 |
38 contaminants tested, none detected
Utility contact
Frequently asked questions about Cal Am Water Company - Hidden Hills
Is Cal Am Water Company - Hidden Hills tap water safe to drink?
EPA monitoring detected 16 contaminants in Cal Am Water Company - Hidden Hills's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cal Am Water Company - Hidden Hills's water?
EPA monitoring detected Lead, Nitrate, Arsenic, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Cal Am Water Company - Hidden Hills serve?
Cal Am Water Company - Hidden Hills reports serving 1,106 people in California, per its EPA record.
Has Cal Am Water Company - Hidden Hills had any water quality violations?
The EPA has no formal drinking-water violations on file for Cal Am Water Company - Hidden Hills.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.