Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 1992-07-01 → 2000-03-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 11000 µg/L 110% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 17628 µg/L | 2744/2744 | SYR4 | 2012–2019 |
| Trichloroethylene | 28 µg/L 560% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 57 µg/L | 2517/2820 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 24 µg/L 480% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 58 µg/L | 1892/2820 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 1.8 µg/L 36% of the EPA limit 5 µg/L
worst single sample: 3.2 µg/L | 681/2775 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 5.3 µg/L 76% of the EPA limit 7 µg/L
worst single sample: 9.4 µg/L | 417/650 | SYR4 | 2012–2019 |
| Arsenic | 2.8 µg/L 28% of the EPA limit 10 µg/L
worst single sample: 7.6 µg/L | 368/700 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 4.1 µg/L 5.9% of the EPA limit 70 µg/L
worst single sample: 6.5 µg/L | 190/340 | SYR4 | 2012–2019 |
| Fluoride | 360 µg/L 9% of the EPA limit 4000 µg/L
worst single sample: 380 µg/L | 135/135 | SYR4 | 2012–2019 |
| Barium | 200 µg/L 10% of the EPA limit 2000 µg/L
worst single sample: 210 µg/L | 134/135 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 11850 µg/L 119% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 14000 µg/L | 64/64 | SYR4 | 2016–2019 |
| TTHM | 6.85 µg/L 8.6% of the EPA limit 80 µg/L
worst single sample: 25 µg/L | 56/95 | SYR4 | 2012–2019 |
| Combined Uranium | 5.3938 µg/L 18% of the EPA limit 30 µg/L
worst single sample: 6.556 µg/L | 14/14 | SYR4 | 2012–2018 |
| Dibromochloromethane | 4.62 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 13/95 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2013 |
| Total Haloacetic Acids (HAA5) | 2.635 µg/L 4.4% of the EPA limit 60 µg/L
worst single sample: 3.4 µg/L | 10/95 | SYR4 | 2012–2019 |
| Bromoform | 13.005 µg/L No EPA limit set
worst single sample: 15 µg/L | 8/95 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.7 µg/L No EPA limit set | 7/95 | SYR4 | 2012–2019 |
| trans-1,2-Dichloroethylene | 6.48 µg/L 6.5% of the EPA limit 100 µg/L
worst single sample: 7 µg/L | 5/178 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.165 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 4/95 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.21 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 3/95 | SYR4 | 2012–2019 |
| 1,2-Dichloroethane | 0.5000 µg/L 10% of the EPA limit 5 µg/L | 1/1020 | SYR4 | 2012–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about California Domestic Water Company
Is California Domestic Water Company tap water safe to drink?
EPA monitoring detected 21 contaminants in California Domestic Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in California Domestic Water Company's water?
EPA monitoring detected Nitrate, Trichloroethylene, Tetrachloroethylene, Carbon Tetrachloride, 1,1-Dichloroethylene, and others. The full list with the level and data source for each is above.
How many people does California Domestic Water Company serve?
California Domestic Water Company reports serving 0 people in California, per its EPA record.
Has California Domestic Water Company had any water quality violations?
The EPA has 1 violation on file for California Domestic Water Company, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.