← California

Tap water quality report

Cal/Am Water Company - San Marino

EPA monitoring tested this supplier for 112 contaminants and detected 27. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
27
detected
47,995
people served
0
health-based violations
Water source
SWP
Ownership
Private
Counties served
Los Angeles

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
2
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2020-01-01 → 2020-03-06
MR Monitoring Resolved 2020-01-01 → 2020-03-06

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0053 µg/L 1/16 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
10353.1 µg/L 104%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 16600 µg/L
4372/4410 SYR4 2012–2019
Trichloroethylene
2.8 µg/L 56%
of the EPA limit 5 µg/L
worst single sample: 6.1 µg/L
1222/1663 SYR4 2012–2019
Tetrachloroethylene
6.5 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 17 µg/L
1179/1685 SYR4 2012–2019
Dibromochloromethane
11.46 µg/L
No EPA limit set
worst single sample: 17.2 µg/L
285/810 SYR4 2012–2019
Bromodichloromethane
12.645 µg/L
No EPA limit set
worst single sample: 17.1 µg/L
232/795 SYR4 2012–2019
Carbon Tetrachloride
0.8000 µg/L 16%
of the EPA limit 5 µg/L
worst single sample: 1.1 µg/L
232/1605 SYR4 2012–2019
Bromoform
4.89 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
203/832 SYR4 2012–2019
Chloroform
12.88 µg/L
No EPA limit set
worst single sample: 15.9 µg/L
193/772 SYR4 2012–2019
TTHM
24.6 µg/L 31%
of the EPA limit 80 µg/L
worst single sample: 43 µg/L
125/139 SYR4 2012–2019
Fluoride
990 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1080 µg/L
123/123 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
20 µg/L 33%
of the EPA limit 60 µg/L
worst single sample: 29 µg/L
59/124 SYR4 2012–2019
Dichloroacetic Acid
9.95 µg/L
No EPA limit set
worst single sample: 12 µg/L
51/124 SYR4 2012–2019
Dibromoacetic Acid
4.41 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
50/124 SYR4 2012–2019
Nitrate-Nitrite
15000 µg/L 150%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 16000 µg/L
38/38 SYR4 2016–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
37/37 LCR 2023
Trichloroacetic Acid
9.855 µg/L
No EPA limit set
worst single sample: 13 µg/L
32/124 SYR4 2012–2019
Combined Uranium
14.2444 µg/L 47%
of the EPA limit 30 µg/L
worst single sample: 23.84 µg/L
25/25 SYR4 2013–2019
Chromium
18.4 µg/L 18%
of the EPA limit 100 µg/L
worst single sample: 44 µg/L
23/135 SYR4 2012–2019
Arsenic
2.9 µg/L 29%
of the EPA limit 10 µg/L
15/123 SYR4 2012–2019
cis-1,2-Dichloroethylene
1.04 µg/L 1.5%
of the EPA limit 70 µg/L
worst single sample: 1.1 µg/L
5/1604 SYR4 2012–2019
Lithium
91.9 µg/L
No EPA limit set
4/16 UCMR-5 2025
1,2-Dichloropropane
2.77 µg/L 55%
of the EPA limit 5 µg/L
worst single sample: 2.9 µg/L
3/1618 SYR4 2012–2019
Copper
153.3 µg/L 12%
of the EPA limit 1300 µg/L
worst single sample: 160 µg/L
2/97 SYR4 2012–2019
Mercury
2.01 µg/L 100%
of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.1 µg/L
2/120 SYR4 2012–2019
Lead
1 µg/L 6.7%
of the EPA limit 15 µg/L
1/97 SYR4 2012–2019
Monochloroacetic Acid
3 µg/L
No EPA limit set
1/124 SYR4 2012–2019
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneVinyl ChlorideXylenes, TotalO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
NIETO, CHRISTOPHER
Phone
626-614-2509
Email
[email protected]

Frequently asked questions about Cal/Am Water Company - San Marino

Is Cal/Am Water Company - San Marino tap water safe to drink?

EPA monitoring detected 27 contaminants in Cal/Am Water Company - San Marino's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Cal/Am Water Company - San Marino's water?

EPA monitoring detected Nitrate, Trichloroethylene, Tetrachloroethylene, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Cal/Am Water Company - San Marino serve?

Cal/Am Water Company - San Marino reports serving 47,995 people in California, per its EPA record.

Has Cal/Am Water Company - San Marino had any water quality violations?

The EPA has 2 violations on file for Cal/Am Water Company - San Marino, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.