Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5700 µg/L 57% of the EPA limit 10000 µg/L
worst single sample: 6780 µg/L | 1444/1464 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 2.795 µg/L 56% of the EPA limit 5 µg/L
worst single sample: 5.8 µg/L | 222/2234 | SYR4 | 2012–2019 |
| Trichloroethylene | 2.3 µg/L 46% of the EPA limit 5 µg/L
worst single sample: 2.6 µg/L | 174/2234 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.8000 µg/L 16% of the EPA limit 5 µg/L
worst single sample: 1.2 µg/L | 120/2234 | SYR4 | 2012–2019 |
| TTHM | 66.98 µg/L 84% of the EPA limit 80 µg/L
worst single sample: 103.8 µg/L | 113/128 | SYR4 | 2012–2019 |
| Dibromochloromethane | 11.28 µg/L No EPA limit set
worst single sample: 16.3 µg/L | 109/125 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17.9 µg/L No EPA limit set
worst single sample: 27.1 µg/L | 101/125 | SYR4 | 2012–2019 |
| Bromoform | 4.445 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 92/125 | SYR4 | 2012–2019 |
| Chloroform | 39.485 µg/L No EPA limit set
worst single sample: 88.2 µg/L | 84/125 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 40.345 µg/L 67% of the EPA limit 60 µg/L
worst single sample: 136 µg/L | 70/121 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 19.575 µg/L No EPA limit set
worst single sample: 50.6 µg/L | 66/121 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.625 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 56/121 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 40.63 µg/L No EPA limit set
worst single sample: 83.2 µg/L | 34/121 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 28/28 | LCR | 2022 |
| Fluoride | 2780 µg/L 70% of the EPA limit 4000 µg/L
worst single sample: 3000 µg/L | 25/25 | SYR4 | 2012–2019 |
| Arsenic | 4.52 µg/L 45% of the EPA limit 10 µg/L
worst single sample: 4.8 µg/L | 9/14 | SYR4 | 2012–2019 |
| Combined Uranium | 11.9126 µg/L 40% of the EPA limit 30 µg/L
worst single sample: 12.069 µg/L | 8/8 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 3.31 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 7/121 | SYR4 | 2012–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Lincoln Avenue Water Co.
Is Lincoln Avenue Water Co. tap water safe to drink?
EPA monitoring detected 18 contaminants in Lincoln Avenue Water Co.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lincoln Avenue Water Co.'s water?
EPA monitoring detected Nitrate, Carbon Tetrachloride, Trichloroethylene, Tetrachloroethylene, TTHM, and others. The full list with the level and data source for each is above.
How many people does Lincoln Avenue Water Co. serve?
Lincoln Avenue Water Co. reports serving 16,088 people in California, per its EPA record.
Has Lincoln Avenue Water Co. had any water quality violations?
The EPA has no formal drinking-water violations on file for Lincoln Avenue Water Co..
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.