← California

Tap water quality report

Huntington Park-City, Water Dept.

EPA monitoring tested this supplier for 82 contaminants and detected 26. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
26
detected
15,437
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Los Angeles

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
1
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Archived 1987-09-01 → 1987-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFHXS 0.0051 µg/L 2/14 2024
PFOA 0.0051 µg/L 2/14 2024
PFOS 0.0230 µg/L 2/14 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Trichloroethylene
2.255 µg/L 45%
of the EPA limit 5 µg/L
worst single sample: 4.1 µg/L
250/773 SYR4 2012–2019
Nitrate
12000 µg/L 120%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 12430 µg/L
242/266 SYR4 2012–2019
TTHM
60.655 µg/L 76%
of the EPA limit 80 µg/L
worst single sample: 72.8 µg/L
124/219 SYR4 2012–2019
Bromoform
10.69 µg/L
No EPA limit set
worst single sample: 20.2 µg/L
123/219 SYR4 2012–2019
Dibromochloromethane
21.21 µg/L
No EPA limit set
worst single sample: 30.4 µg/L
118/219 SYR4 2012–2019
Bromodichloromethane
16.5 µg/L
No EPA limit set
worst single sample: 22.9 µg/L
116/219 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
21.85 µg/L 36%
of the EPA limit 60 µg/L
worst single sample: 24.5 µg/L
106/127 SYR4 2012–2019
Dibromoacetic Acid
6.6 µg/L
No EPA limit set
worst single sample: 9.8 µg/L
102/127 SYR4 2012–2019
Chloroform
19.72 µg/L
No EPA limit set
worst single sample: 22 µg/L
99/219 SYR4 2012–2019
Dichloroacetic Acid
10.6 µg/L
No EPA limit set
worst single sample: 11.4 µg/L
97/127 SYR4 2012–2019
Carbon Tetrachloride
3.15 µg/L 63%
of the EPA limit 5 µg/L
worst single sample: 3.8 µg/L
91/134 SYR4 2012–2019
Trichloroacetic Acid
6.7 µg/L
No EPA limit set
worst single sample: 7.3 µg/L
78/127 SYR4 2012–2019
Tetrachloroethylene
1.1 µg/L 22%
of the EPA limit 5 µg/L
worst single sample: 1.3 µg/L
66/134 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
32/32 LCR 2025
Fluoride
431.5 µg/L 11%
of the EPA limit 4000 µg/L
worst single sample: 440 µg/L
18/18 SYR4 2012–2019
Barium
150 µg/L 7.5%
of the EPA limit 2000 µg/L
11/17 SYR4 2012–2019
Combined Uranium
14.1624 µg/L 47%
of the EPA limit 30 µg/L
worst single sample: 14.9 µg/L
10/11 SYR4 2013–2019
Monobromoacetic Acid
1.3 µg/L
No EPA limit set
4/127 SYR4 2012–2019
Lithium
54 µg/L
No EPA limit set
4/14 UCMR-5 2024
Arsenic
2.89 µg/L 29%
of the EPA limit 10 µg/L
worst single sample: 2.9 µg/L
3/19 SYR4 2012–2019
Monochloroacetic Acid
2.49 µg/L
No EPA limit set
worst single sample: 2.5 µg/L
2/127 SYR4 2012–2019
Nitrate-Nitrite
663000 µg/L 6630%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 670000 µg/L
2/3 SYR4 2013
Selenium
6.655 µg/L 13%
of the EPA limit 50 µg/L
worst single sample: 6.7 µg/L
2/17 SYR4 2012–2019
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosBenzeneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumChromiumDichloromethaneDi(2-ethylhexyl) PhthalateEthylbenzeneHfpo-DaLeadMercuryNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPfpeaPfpesPftaPftrdaPfunaStyreneThallium, TotalTolueneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LOPEZ, GERARDO
Phone
323-584-6274
Email
[email protected]

Frequently asked questions about Huntington Park-City, Water Dept.

Is Huntington Park-City, Water Dept. tap water safe to drink?

EPA monitoring detected 26 contaminants in Huntington Park-City, Water Dept.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Huntington Park-City, Water Dept.'s water?

EPA monitoring detected Trichloroethylene, Nitrate, TTHM, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Huntington Park-City, Water Dept. serve?

Huntington Park-City, Water Dept. reports serving 15,437 people in California, per its EPA record.

Has Huntington Park-City, Water Dept. had any water quality violations?

The EPA has 1 violation on file for Huntington Park-City, Water Dept., of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.