← Arizona

Tap water quality report

Sun Leisure Estates Improvement District

EPA monitoring tested this supplier for 71 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
13
detected
143
people served
90
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Yuma

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

90
health-based violations
367
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Combined Uranium
54.14 µg/L 180%
of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 65.262 µg/L
28/31 SYR4 2012–2019
Copper
98 µg/L 7.5%
of the EPA limit 1300 µg/L
worst single sample: 130 µg/L
27/38 SYR4 2012–2018
Nitrate
5490 µg/L 55%
of the EPA limit 10000 µg/L
worst single sample: 5500 µg/L
22/22 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Gross Alpha, Excl. Radon And U
6.95 pCi/L 46%
of the EPA limit 15 pCi/L
worst single sample: 8.9 pCi/L
14/25 SYR4 2012–2018
Lead
17.2 µg/L 115%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 19 µg/L
7/38 SYR4 2012–2018
Combined Radium (-226 And -228)
1.74 pCi/L 35%
of the EPA limit 5 pCi/L
worst single sample: 1.9 pCi/L
5/30 SYR4 2012–2019
Nitrate-Nitrite
5277.5 µg/L 53%
of the EPA limit 10000 µg/L
worst single sample: 5300 µg/L
4/4 SYR4 2012–2013
Arsenic
4.4 µg/L 44%
of the EPA limit 10 µg/L
worst single sample: 4.5 µg/L
2/2 SYR4 2013–2019
Barium
23.95 µg/L 1.2%
of the EPA limit 2000 µg/L
worst single sample: 24 µg/L
2/2 SYR4 2013–2019
Fluoride
866.5 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 870 µg/L
2/2 SYR4 2013–2019
Selenium
11.875 µg/L 24%
of the EPA limit 50 µg/L
worst single sample: 12 µg/L
2/2 SYR4 2013–2019
Chromium
1.9 µg/L 1.9%
of the EPA limit 100 µg/L
1/2 SYR4 2013–2019
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
STALLWORTH, RACHEL
Phone
928-341-2511
Email
[email protected]

Frequently asked questions about Sun Leisure Estates Improvement District

Is Sun Leisure Estates Improvement District tap water safe to drink?

EPA monitoring detected 13 contaminants in Sun Leisure Estates Improvement District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Sun Leisure Estates Improvement District's water?

EPA monitoring detected Combined Uranium, Copper, Nitrate, Lead, Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.

How many people does Sun Leisure Estates Improvement District serve?

Sun Leisure Estates Improvement District reports serving 143 people in Arizona, per its EPA record.

Has Sun Leisure Estates Improvement District had any water quality violations?

The EPA has 367 violations on file for Sun Leisure Estates Improvement District, of which 90 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.