← Arizona

Tap water quality report

Foothills Water and Sewer Llc

EPA monitoring tested this supplier for 106 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

106
contaminants tested
17
detected
32,425
people served
27
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Yuma

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

27
health-based violations
1,801
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2019-04-01
TT Health-based Resolved 2019-04-01
TT Health-based Resolved 2019-04-01
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
TT Health-based Resolved 2015-03-01 → 2015-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
100 µg/L 125%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 120 µg/L
129/131 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
36 µg/L 60%
of the EPA limit 60 µg/L
worst single sample: 44 µg/L
123/128 SYR4 2012–2019
Copper
67.85 µg/L 5.2%
of the EPA limit 1300 µg/L
worst single sample: 590 µg/L
84/89 SYR4 2013–2019
Nitrate
7430 µg/L 74%
of the EPA limit 10000 µg/L
worst single sample: 8100 µg/L
78/96 SYR4 2012–2019
Nitrate-Nitrite
7460 µg/L 75%
of the EPA limit 10000 µg/L
worst single sample: 8100 µg/L
35/44 SYR4 2012–2019
Arsenic
6.82 µg/L 68%
of the EPA limit 10 µg/L
worst single sample: 8.9 µg/L
23/33 SYR4 2012–2019
Lithium
94.9 µg/L
No EPA limit set
20/20 UCMR-5 2024
Barium
431 µg/L 22%
of the EPA limit 2000 µg/L
worst single sample: 760 µg/L
15/15 SYR4 2013–2019
Lead
21.4 µg/L 143%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 28 µg/L
13/89 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Selenium
3.775 µg/L 7.6%
of the EPA limit 50 µg/L
worst single sample: 4.2 µg/L
6/15 SYR4 2013–2019
Combined Uranium
11.14 µg/L 37%
of the EPA limit 30 µg/L
worst single sample: 12.3 µg/L
5/5 SYR4 2013
Gross Alpha, Excl. Radon And U
3.32 pCi/L 22%
of the EPA limit 15 pCi/L
worst single sample: 3.4 pCi/L
5/5 SYR4 2013
Chlorite
249 µg/L 25%
of the EPA limit 1000 µg/L
worst single sample: 250 µg/L
3/3 SYR4 2015
Di(2-ethylhexyl) Phthalate
4.41 µg/L 74%
of the EPA limit 6 µg/L
worst single sample: 4.5 µg/L
3/55 SYR4 2012–2019
Chromium
3.1 µg/L 3.1%
of the EPA limit 100 µg/L
worst single sample: 3.2 µg/L
2/15 SYR4 2013–2019
Fluoride
509 µg/L 13%
of the EPA limit 4000 µg/L
worst single sample: 510 µg/L
2/17 SYR4 2013–2019
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FERRO, WILLIAM
Phone
928-581-3321
Email
[email protected]

Frequently asked questions about Foothills Water and Sewer Llc

Is Foothills Water and Sewer Llc tap water safe to drink?

EPA monitoring detected 17 contaminants in Foothills Water and Sewer Llc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Foothills Water and Sewer Llc's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Nitrate, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Foothills Water and Sewer Llc serve?

Foothills Water and Sewer Llc reports serving 32,425 people in Arizona, per its EPA record.

Has Foothills Water and Sewer Llc had any water quality violations?

The EPA has 1801 violations on file for Foothills Water and Sewer Llc, of which 27 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.