Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2004-08-01 → 2004-08-31 |
| MCL | Health-based | Resolved | 2002-05-01 → 2002-05-31 |
| MCL | Health-based | Resolved | 2001-10-01 → 2001-10-31 |
| MCL | Health-based | Resolved | 2001-07-01 → 2001-07-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5825 µg/L 58% of the EPA limit 10000 µg/L
worst single sample: 6200 µg/L | 146/146 | SYR4 | 2012–2019 |
| Copper | 435 µg/L 33% of the EPA limit 1300 µg/L
worst single sample: 990 µg/L | 67/90 | SYR4 | 2012–2018 |
| Lead | 5.42 µg/L 36% of the EPA limit 15 µg/L
worst single sample: 8.2 µg/L | 39/90 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 5475 µg/L 55% of the EPA limit 10000 µg/L
worst single sample: 6200 µg/L | 26/26 | SYR4 | 2013–2019 |
| Fluoride | 2760 µg/L 69% of the EPA limit 4000 µg/L
worst single sample: 3200 µg/L | 23/26 | SYR4 | 2013–2019 |
| Lithium | 580 µg/L No EPA limit set | 18/18 | UCMR-5 | 2024 |
| Arsenic | 8.26 µg/L 83% of the EPA limit 10 µg/L
worst single sample: 8.9 µg/L | 17/25 | SYR4 | 2013–2019 |
| TTHM | 18.4 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 20 µg/L | 17/24 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.64 pCi/L 33% of the EPA limit 5 pCi/L
worst single sample: 2 pCi/L | 13/27 | SYR4 | 2013–2019 |
| Lead | 0.0056 mg/L 37% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Total Haloacetic Acids (HAA5) | 5.1 µg/L 8.5% of the EPA limit 60 µg/L | 12/24 | SYR4 | 2012–2019 |
| Barium | 56.8 µg/L 2.8% of the EPA limit 2000 µg/L
worst single sample: 60 µg/L | 9/26 | SYR4 | 2013–2019 |
| Selenium | 9.04 µg/L 18% of the EPA limit 50 µg/L
worst single sample: 9.4 µg/L | 5/24 | SYR4 | 2013–2019 |
| Chromium | 1.93 µg/L 1.9% of the EPA limit 100 µg/L
worst single sample: 2 µg/L | 3/26 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Adipate | 0.8400 µg/L 0.2% of the EPA limit 400 µg/L | 3/57 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 2.76 µg/L 46% of the EPA limit 6 µg/L
worst single sample: 2.9 µg/L | 3/57 | SYR4 | 2013–2019 |
| Combined Uranium | 2.9 µg/L 9.7% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2019 |
| Gross Alpha, Excl. Radon And U | 1 pCi/L 6.7% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2019 |
| Picloram | 0.1000 µg/L 0% of the EPA limit 500 µg/L | 1/48 | SYR4 | 2013–2019 |
| Toluene | 0.7000 µg/L 0.1% of the EPA limit 1000 µg/L | 1/29 | SYR4 | 2013–2019 |
80 contaminants tested, none detected
Utility contact
Frequently asked questions about Bermuda Water Company Inc
Is Bermuda Water Company Inc tap water safe to drink?
EPA monitoring detected 23 contaminants in Bermuda Water Company Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bermuda Water Company Inc's water?
EPA monitoring detected Nitrate, Copper, Lead, Nitrate-Nitrite, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Bermuda Water Company Inc serve?
Bermuda Water Company Inc reports serving 25,000 people in Arizona, per its EPA record.
Has Bermuda Water Company Inc had any water quality violations?
The EPA has 1488 violations on file for Bermuda Water Company Inc, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.