← Arizona

Tap water quality report

Epcor - Sun City West

EPA monitoring tested this supplier for 102 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
15
detected
25,796
people served
3
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Maricopa

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

3
health-based violations
109
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2001-08-01 → 2001-08-31
MCL Health-based Archived 1988-10-01 → 1988-12-31
MCL Health-based Archived 1988-04-01 → 1988-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2022-01-01 → 2022-12-31
MR Monitoring Resolved 2018-01-01 → 2018-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
7.685 µg/L 77%
of the EPA limit 10 µg/L
worst single sample: 9.7 µg/L
64/64 SYR4 2012–2019
Copper
240 µg/L 18%
of the EPA limit 1300 µg/L
worst single sample: 310 µg/L
61/61 SYR4 2014–2017
Nitrate
4557 µg/L 46%
of the EPA limit 10000 µg/L
worst single sample: 4830 µg/L
34/34 SYR4 2012–2019
TTHM
4.805 µg/L 6%
of the EPA limit 80 µg/L
worst single sample: 6.2 µg/L
34/34 SYR4 2012–2019
Nitrate-Nitrite
4578 µg/L 46%
of the EPA limit 10000 µg/L
worst single sample: 4830 µg/L
13/13 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Total Haloacetic Acids (HAA5)
2.56 µg/L 4.3%
of the EPA limit 60 µg/L
worst single sample: 2.6 µg/L
9/34 SYR4 2012–2019
Fluoride
1990 µg/L 50%
of the EPA limit 4000 µg/L
worst single sample: 2080 µg/L
6/6 SYR4 2012–2018
Selenium
4.925 µg/L 9.9%
of the EPA limit 50 µg/L
worst single sample: 5 µg/L
6/6 SYR4 2012–2018
1,2-DIBROMO-3-CHLOROPROPANE
0.0300 µg/L 15%
of the EPA limit 0.2000 µg/L
4/16 SYR4 2012–2018
Chromium
7 µg/L 7%
of the EPA limit 100 µg/L
4/6 SYR4 2012–2018
Lead
16.115 µg/L 107%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 17.9 µg/L
4/61 SYR4 2014–2017
Lithium
132 µg/L
No EPA limit set
4/4 UCMR-5 2023
Barium
30.9 µg/L 1.5%
of the EPA limit 2000 µg/L
worst single sample: 31 µg/L
3/6 SYR4 2012–2018
Combined Radium (-226 And -228)
0.5000 pCi/L 10%
of the EPA limit 5 pCi/L
1/9 SYR4 2015–2019
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DIDOMIZIO, TOM
Phone
623-445-2431
Email
[email protected]

Frequently asked questions about Epcor - Sun City West

Is Epcor - Sun City West tap water safe to drink?

EPA monitoring detected 15 contaminants in Epcor - Sun City West's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Epcor - Sun City West's water?

EPA monitoring detected Arsenic, Copper, Nitrate, TTHM, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Epcor - Sun City West serve?

Epcor - Sun City West reports serving 25,796 people in Arizona, per its EPA record.

Has Epcor - Sun City West had any water quality violations?

The EPA has 109 violations on file for Epcor - Sun City West, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.