Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Resolved | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Resolved | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Resolved | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Resolved | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Resolved | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Resolved | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Resolved | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Resolved | 2024-04-01 → 2024-06-30 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 22.965 µg/L No EPA limit set
worst single sample: 29.2 µg/L | 64/64 | SYR4 | 2012–2019 |
| Chloroform | 83.675 µg/L No EPA limit set
worst single sample: 95.5 µg/L | 64/64 | SYR4 | 2012–2019 |
| TTHM | 97.915 µg/L 122% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 107 µg/L | 64/64 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.57 µg/L No EPA limit set
worst single sample: 45.4 µg/L | 63/64 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 64.69 µg/L 108% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 88.7 µg/L | 63/64 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 31.54 µg/L No EPA limit set
worst single sample: 38.4 µg/L | 63/64 | SYR4 | 2012–2019 |
| Dibromochloromethane | 18.525 µg/L No EPA limit set
worst single sample: 25.5 µg/L | 38/64 | SYR4 | 2012–2019 |
| Bromoform | 4.755 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 28/64 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.595 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 22/64 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.85 µg/L No EPA limit set
worst single sample: 12.6 µg/L | 19/64 | SYR4 | 2012–2019 |
| Copper | 189.6 µg/L 15% of the EPA limit 1300 µg/L
worst single sample: 210 µg/L | 13/30 | SYR4 | 2012–2018 |
| Lead | 0.0070 mg/L 47% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2003 |
| Monobromoacetic Acid | 4.66 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 7/64 | SYR4 | 2012–2019 |
| Lead | 1 µg/L 6.7% of the EPA limit 15 µg/L | 2/30 | SYR4 | 2012–2018 |
Utility contact
Frequently asked questions about East Logan Co Rural Water
Is East Logan Co Rural Water tap water safe to drink?
EPA monitoring detected 14 contaminants in East Logan Co Rural Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in East Logan Co Rural Water's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does East Logan Co Rural Water serve?
East Logan Co Rural Water reports serving 2,263 people in Arkansas, per its EPA record.
Has East Logan Co Rural Water had any water quality violations?
The EPA has 61 violations on file for East Logan Co Rural Water, of which 53 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.