Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-07-01 → 2024-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 15.265 µg/L No EPA limit set
worst single sample: 17.9 µg/L | 50/50 | SYR4 | 2013–2019 |
| Chloroform | 81.83 µg/L No EPA limit set
worst single sample: 88.4 µg/L | 50/50 | SYR4 | 2013–2019 |
| TTHM | 98.825 µg/L 124% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 106 µg/L | 50/50 | SYR4 | 2013–2019 |
| Dibromochloromethane | 3.8 µg/L No EPA limit set
worst single sample: 4 µg/L | 46/50 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 29.34 µg/L No EPA limit set
worst single sample: 47.3 µg/L | 44/48 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 71.995 µg/L 120% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 110 µg/L | 44/48 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 43.25 µg/L No EPA limit set
worst single sample: 59.4 µg/L | 38/48 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 4.315 µg/L No EPA limit set
worst single sample: 4.9 µg/L | 14/48 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2004 |
| Dibromoacetic Acid | 1.375 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 6/48 | SYR4 | 2013–2019 |
| Copper | 342 µg/L 26% of the EPA limit 1300 µg/L
worst single sample: 350 µg/L | 5/20 | SYR4 | 2013–2019 |
| Lead | 7.925 µg/L 53% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 2/20 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1.2 µg/L No EPA limit set | 1/48 | SYR4 | 2013–2019 |
1 contaminants tested, none detected
Utility contact
Frequently asked questions about Buena Vista-Ogemaw Water Association
Is Buena Vista-Ogemaw Water Association tap water safe to drink?
EPA monitoring detected 13 contaminants in Buena Vista-Ogemaw Water Association's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Buena Vista-Ogemaw Water Association's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Buena Vista-Ogemaw Water Association serve?
Buena Vista-Ogemaw Water Association reports serving 384 people in Arkansas, per its EPA record.
Has Buena Vista-Ogemaw Water Association had any water quality violations?
The EPA has 124 violations on file for Buena Vista-Ogemaw Water Association, of which 99 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.