← Arkansas

Tap water quality report

Clinton Waterworks

EPA monitoring tested this supplier for 107 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
13
detected
10,280
people served
46
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Van Buren

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

46
health-based violations
53
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2013-01-01 → 2013-01-31
TT Health-based Resolved 2013-01-01 → 2013-01-31
TT Health-based Resolved 2013-01-01 → 2013-01-31
TT Health-based Resolved 2013-01-01 → 2013-01-31
TT Health-based Resolved 2013-01-01 → 2013-01-31
TT Health-based Resolved 2011-11-01 → 2011-11-30
TT Health-based Resolved 2011-11-01 → 2011-11-30
TT Health-based Resolved 2011-11-01 → 2011-11-30
TT Health-based Resolved 2011-11-01 → 2011-11-30
TT Health-based Resolved 2011-11-01 → 2011-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
960 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L
104/104 SYR4 2012–2019
Copper
331.5 µg/L 26%
of the EPA limit 1300 µg/L
worst single sample: 417 µg/L
40/60 SYR4 2013–2019
Bromodichloromethane
6.125 µg/L
No EPA limit set
worst single sample: 6.4 µg/L
26/26 SYR4 2012–2019
Chloroform
36.175 µg/L
No EPA limit set
worst single sample: 38 µg/L
26/26 SYR4 2012–2019
Dichloroacetic Acid
11.3 µg/L
No EPA limit set
19/19 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
21.93 µg/L 37%
of the EPA limit 60 µg/L
worst single sample: 22.2 µg/L
19/19 SYR4 2012–2019
Trichloroacetic Acid
10.92 µg/L
No EPA limit set
worst single sample: 11.1 µg/L
19/19 SYR4 2012–2019
TTHM
42.32 µg/L 53%
of the EPA limit 80 µg/L
worst single sample: 43 µg/L
18/18 SYR4 2012–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Nitrate-Nitrite
400 µg/L 4%
of the EPA limit 10000 µg/L
12/16 SYR4 2012–2019
Lead
18 µg/L 120%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 20 µg/L
11/68 SYR4 2012–2019
Dibromochloromethane
1.13525 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
6/31 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
2.34 µg/L 39%
of the EPA limit 6 µg/L
1/13 SYR4 2012–2019
94 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HINCHEY, JACKIE
Phone
501-745-2206
Email
[email protected]

Frequently asked questions about Clinton Waterworks

Is Clinton Waterworks tap water safe to drink?

EPA monitoring detected 13 contaminants in Clinton Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Clinton Waterworks's water?

EPA monitoring detected Fluoride, Copper, Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Clinton Waterworks serve?

Clinton Waterworks reports serving 10,280 people in Arkansas, per its EPA record.

Has Clinton Waterworks had any water quality violations?

The EPA has 53 violations on file for Clinton Waterworks, of which 46 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.