Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-05-01 → 2008-05-31 |
| MCL | Health-based | Resolved | 2008-05-01 → 2008-05-31 |
| MCL | Health-based | Resolved | 2008-05-01 → 2008-05-31 |
| MR | Monitoring | Resolved | 2009-02-01 → 2009-02-28 |
| MR | Monitoring | Resolved | 2009-02-01 → 2009-02-28 |
| MR | Monitoring | Resolved | 2008-06-01 → 2008-06-30 |
| MR | Monitoring | Resolved | 2008-06-01 → 2008-06-30 |
| MR | Monitoring | Resolved | 2008-06-01 → 2008-06-30 |
| Other | Monitoring | Archived | 1996-06-01 → 1996-06-30 |
| MR | Monitoring | Archived | 1995-03-01 → 1995-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Dichloroacetic Acid | 22.775 µg/L No EPA limit set
worst single sample: 25.2 µg/L | 56/56 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 57.35 µg/L 96% of the EPA limit 60 µg/L
worst single sample: 61.3 µg/L | 56/56 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 33.1 µg/L No EPA limit set
worst single sample: 37.7 µg/L | 56/56 | SYR4 | 2012–2019 |
| Bromodichloromethane | 8.6 µg/L No EPA limit set
worst single sample: 9.2 µg/L | 54/54 | SYR4 | 2012–2019 |
| Chloroform | 61.36 µg/L No EPA limit set
worst single sample: 79.7 µg/L | 54/54 | SYR4 | 2012–2019 |
| TTHM | 68.825 µg/L 86% of the EPA limit 80 µg/L
worst single sample: 85.3 µg/L | 54/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.96 µg/L No EPA limit set
worst single sample: 5.7 µg/L | 28/56 | SYR4 | 2012–2019 |
| Copper | 177.8 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 442 µg/L | 27/60 | SYR4 | 2012–2018 |
| Lead | 12 µg/L 80% of the EPA limit 15 µg/L
worst single sample: 24.5 µg/L | 21/60 | SYR4 | 2012–2018 |
| Dibromochloromethane | 1.72 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 19/54 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Monobromoacetic Acid | 1.475 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 2/56 | SYR4 | 2012–2019 |
32 contaminants tested, none detected
Utility contact
Frequently asked questions about Madison Co Water Facilities Bd
Is Madison Co Water Facilities Bd tap water safe to drink?
EPA monitoring detected 12 contaminants in Madison Co Water Facilities Bd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Madison Co Water Facilities Bd's water?
EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Madison Co Water Facilities Bd serve?
Madison Co Water Facilities Bd reports serving 11,435 people in Arkansas, per its EPA record.
Has Madison Co Water Facilities Bd had any water quality violations?
The EPA has 15 violations on file for Madison Co Water Facilities Bd, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.