Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 6.5 µg/L No EPA limit set
worst single sample: 8 µg/L | 112/112 | SYR4 | 2012–2019 |
| Chloroform | 67.035 µg/L No EPA limit set
worst single sample: 83 µg/L | 112/112 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 24.995 µg/L No EPA limit set
worst single sample: 30.6 µg/L | 104/104 | SYR4 | 2012–2019 |
| TTHM | 73.3 µg/L 92% of the EPA limit 80 µg/L
worst single sample: 90.5 µg/L | 104/104 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 52.4 µg/L 87% of the EPA limit 60 µg/L
worst single sample: 61.5 µg/L | 104/104 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 24.325 µg/L No EPA limit set
worst single sample: 30.7 µg/L | 104/104 | SYR4 | 2012–2019 |
| Fluoride | 665.5 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 740 µg/L | 70/73 | SYR4 | 2012–2019 |
| Copper | 565 µg/L 43% of the EPA limit 1300 µg/L
worst single sample: 1000 µg/L | 51/60 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 3.74 µg/L No EPA limit set
worst single sample: 6.1 µg/L | 29/104 | SYR4 | 2012–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Lead | 4.73 µg/L 32% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 10/68 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.4355 µg/L No EPA limit set
worst single sample: 0.4360 µg/L | 6/118 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.1 µg/L No EPA limit set | 3/104 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.955 µg/L No EPA limit set
worst single sample: 2 µg/L | 2/104 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 120 µg/L 1.2% of the EPA limit 10000 µg/L | 2/16 | SYR4 | 2012–2019 |
| Diquat | 2.3 µg/L 12% of the EPA limit 20 µg/L | 1/13 | SYR4 | 2012–2019 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Hot Springs Village Waterworks
Is Hot Springs Village Waterworks tap water safe to drink?
EPA monitoring detected 16 contaminants in Hot Springs Village Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hot Springs Village Waterworks's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Hot Springs Village Waterworks serve?
Hot Springs Village Waterworks reports serving 15,985 people in Arkansas, per its EPA record.
Has Hot Springs Village Waterworks had any water quality violations?
The EPA has no formal drinking-water violations on file for Hot Springs Village Waterworks.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.