Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2012-01-01 → 2012-03-31 |
| MCL | Health-based | Resolved | 2010-07-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-07-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-07-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-06-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-06-30 |
| MCL | Health-based | Resolved | 2010-04-01 → 2010-06-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 7.13 µg/L No EPA limit set
worst single sample: 7.6 µg/L | 55/55 | SYR4 | 2012–2019 |
| Chloroform | 75.02 µg/L No EPA limit set
worst single sample: 95.7 µg/L | 55/55 | SYR4 | 2012–2019 |
| TTHM | 79.62 µg/L 100% of the EPA limit 80 µg/L
worst single sample: 103 µg/L | 55/55 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.905 µg/L No EPA limit set
worst single sample: 39.1 µg/L | 54/55 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 69.185 µg/L 115% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 86.2 µg/L | 54/55 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 36.995 µg/L No EPA limit set
worst single sample: 44.4 µg/L | 54/55 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.19 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 23/55 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2007 |
| Copper | 187.2 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 212 µg/L | 9/20 | SYR4 | 2014–2017 |
| Lead | 11 µg/L 73% of the EPA limit 15 µg/L
worst single sample: 13 µg/L | 6/20 | SYR4 | 2014–2017 |
| Dibromochloromethane | 1.395 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 2/55 | SYR4 | 2012–2019 |
33 contaminants tested, none detected
Utility contact
Frequently asked questions about Guy Waterworks
Is Guy Waterworks tap water safe to drink?
EPA monitoring detected 11 contaminants in Guy Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Guy Waterworks's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Guy Waterworks serve?
Guy Waterworks reports serving 2,438 people in Arkansas, per its EPA record.
Has Guy Waterworks had any water quality violations?
The EPA has 33 violations on file for Guy Waterworks, of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.