Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Dichloroacetic Acid | 19.385 µg/L No EPA limit set
worst single sample: 24.8 µg/L | 60/60 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 35.855 µg/L 60% of the EPA limit 60 µg/L
worst single sample: 43.1 µg/L | 60/60 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 19.045 µg/L No EPA limit set
worst single sample: 24 µg/L | 60/60 | SYR4 | 2012–2019 |
| Bromodichloromethane | 13.715 µg/L No EPA limit set
worst single sample: 15.1 µg/L | 58/58 | SYR4 | 2012–2019 |
| Chloroform | 69.35 µg/L No EPA limit set
worst single sample: 85 µg/L | 58/58 | SYR4 | 2012–2019 |
| TTHM | 85.49 µg/L 107% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 99.3 µg/L | 58/58 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.2 µg/L No EPA limit set
worst single sample: 6.1 µg/L | 52/58 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.73 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 18/60 | SYR4 | 2012–2019 |
| Lead | 39.5 µg/L 263% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 131 µg/L | 16/60 | SYR4 | 2013–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Copper | 345.5 µg/L 27% of the EPA limit 1300 µg/L
worst single sample: 560 µg/L | 12/60 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 3.255 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 8/60 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.92 µg/L No EPA limit set
worst single sample: 2 µg/L | 5/60 | SYR4 | 2012–2019 |
| Bromoform | 1.1 µg/L No EPA limit set | 2/58 | SYR4 | 2012–2019 |
30 contaminants tested, none detected
Utility contact
Frequently asked questions about Cedarville Waterworks Fbcc
Is Cedarville Waterworks Fbcc tap water safe to drink?
EPA monitoring detected 14 contaminants in Cedarville Waterworks Fbcc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cedarville Waterworks Fbcc's water?
EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Cedarville Waterworks Fbcc serve?
Cedarville Waterworks Fbcc reports serving 8,529 people in Arkansas, per its EPA record.
Has Cedarville Waterworks Fbcc had any water quality violations?
The EPA has no formal drinking-water violations on file for Cedarville Waterworks Fbcc.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.