Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-08-01 → 2023-08-31 |
| TT | Health-based | Resolved | 2023-08-01 → 2023-08-31 |
| TT | Health-based | Resolved | 2023-08-01 → 2023-08-31 |
| TT | Health-based | Resolved | 2023-08-01 → 2023-08-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MR | Monitoring | Archived | 2025-07-01 → 2025-09-30 |
| MR | Monitoring | Archived | 2025-07-01 → 2025-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 39.805 µg/L 66% of the EPA limit 60 µg/L
worst single sample: 61.7 µg/L | 834/846 | SYR4 | 2012–2019 |
| TTHM | 59.95 µg/L 75% of the EPA limit 80 µg/L
worst single sample: 105 µg/L | 831/843 | SYR4 | 2012–2019 |
| Chlorite | 700 µg/L 70% of the EPA limit 1000 µg/L
worst single sample: 938 µg/L | 541/546 | SYR4 | 2012–2019 |
| Copper | 159.4 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 958 µg/L | 167/235 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 43/43 | LCR | 2023 |
| Nitrate | 290 µg/L 2.9% of the EPA limit 10000 µg/L
worst single sample: 300 µg/L | 42/46 | SYR4 | 2012–2019 |
| Fluoride | 821 µg/L 21% of the EPA limit 4000 µg/L
worst single sample: 900 µg/L | 23/23 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 290 µg/L 2.9% of the EPA limit 10000 µg/L
worst single sample: 300 µg/L | 21/23 | SYR4 | 2012–2019 |
| Chloroform | 8.2435 µg/L No EPA limit set
worst single sample: 14.2 µg/L | 20/20 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.848 µg/L No EPA limit set
worst single sample: 7.28 µg/L | 19/19 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.366 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 19/20 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 1.2 pCi/L 8% of the EPA limit 15 pCi/L
worst single sample: 1.5 pCi/L | 16/21 | SYR4 | 2012–2019 |
| Lead | 1.95 µg/L 13% of the EPA limit 15 µg/L
worst single sample: 2 µg/L | 2/235 | SYR4 | 2012–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Tuscaloosa Water & Sewer
Is Tuscaloosa Water & Sewer tap water safe to drink?
EPA monitoring detected 13 contaminants in Tuscaloosa Water & Sewer's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Tuscaloosa Water & Sewer's water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Chlorite, Copper, Lead, and others. The full list with the level and data source for each is above.
How many people does Tuscaloosa Water & Sewer serve?
Tuscaloosa Water & Sewer reports serving 166,524 people in Alabama, per its EPA record.
Has Tuscaloosa Water & Sewer had any water quality violations?
The EPA has 41 violations on file for Tuscaloosa Water & Sewer, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.