Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2000-04-01 → 2000-04-30 |
| MCL | Health-based | Archived | 1994-05-01 → 1994-05-31 |
| MCL | Health-based | Archived | 1994-05-01 → 1994-05-31 |
| MCL | Health-based | Archived | 1994-05-01 → 1994-05-31 |
| MCL | Health-based | Archived | 1985-07-01 → 1985-09-30 |
| MCL | Health-based | Archived | 1985-07-01 → 1985-09-30 |
| MCL | Health-based | Archived | 1985-06-01 → 1985-06-30 |
| MCL | Health-based | Archived | 1985-03-01 → 1992-08-31 |
| MCL | Health-based | Archived | 1984-12-01 → 1992-02-29 |
| MCL | Health-based | Archived | 1984-09-01 → 1985-08-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| 6:2 Fts | 0.0084 µg/L | 1/16 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 5.725 µg/L 9.5% of the EPA limit 60 µg/L
worst single sample: 16.9 µg/L | 55/60 | SYR4 | 2012–2019 |
| TTHM | 13.3 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 14.3 µg/L | 53/60 | SYR4 | 2012–2019 |
| Copper | 130.8 µg/L 10% of the EPA limit 1300 µg/L
worst single sample: 222 µg/L | 37/52 | SYR4 | 2013–2019 |
| Nitrate | 317.135 µg/L 3.2% of the EPA limit 10000 µg/L
worst single sample: 455 µg/L | 28/116 | SYR4 | 2012–2019 |
| Fluoride | 1978 µg/L 49% of the EPA limit 4000 µg/L
worst single sample: 2060 µg/L | 22/22 | SYR4 | 2013–2019 |
| Chloroform | 6.92 µg/L No EPA limit set
worst single sample: 10.1 µg/L | 21/28 | SYR4 | 2012–2019 |
| Lead | 2.2 µg/L 15% of the EPA limit 15 µg/L
worst single sample: 2.5 µg/L | 21/52 | SYR4 | 2013–2019 |
| Lead | 0.00099 mg/L 6.6% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| Bromodichloromethane | 3.2075 µg/L No EPA limit set
worst single sample: 6.35 µg/L | 16/28 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.1655 µg/L No EPA limit set
worst single sample: 3.07 µg/L | 10/28 | SYR4 | 2012–2019 |
| Selenium | 4.1205 µg/L 8.2% of the EPA limit 50 µg/L
worst single sample: 6 µg/L | 8/22 | SYR4 | 2013–2019 |
| Antimony, Total | 0.7260 µg/L 12% of the EPA limit 6 µg/L
worst single sample: 0.7500 µg/L | 7/22 | SYR4 | 2013–2019 |
| Barium | 90.27 µg/L 4.5% of the EPA limit 2000 µg/L
worst single sample: 95.4 µg/L | 7/22 | SYR4 | 2013–2019 |
| Arsenic | 1.654 µg/L 17% of the EPA limit 10 µg/L
worst single sample: 2 µg/L | 5/22 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 87.48 µg/L 0.9% of the EPA limit 10000 µg/L
worst single sample: 93.6 µg/L | 4/22 | SYR4 | 2013–2019 |
| Thallium, Total | 0.2760 µg/L 14% of the EPA limit 2 µg/L
worst single sample: 0.2800 µg/L | 3/22 | SYR4 | 2013–2019 |
| Cyanide | 5.2715 µg/L 2.6% of the EPA limit 200 µg/L
worst single sample: 5.39 µg/L | 2/22 | SYR4 | 2013–2019 |
| Lithium | 13.1 µg/L No EPA limit set | 2/16 | UCMR-5 | 2024 |
| Chromium | 0.1700 µg/L 0.2% of the EPA limit 100 µg/L | 1/22 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.2000 pCi/L 4% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2019 |
| Endrin | 0.1300 µg/L 6.5% of the EPA limit 2 µg/L | 1/42 | SYR4 | 2013–2019 |
| Ethylbenzene | 0.2700 µg/L 0% of the EPA limit 700 µg/L | 1/28 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 3 pCi/L 20% of the EPA limit 15 pCi/L | 1/8 | SYR4 | 2016–2019 |
| Nitrite | 46.8 µg/L 4.7% of the EPA limit 1000 µg/L | 1/22 | SYR4 | 2013–2019 |
81 contaminants tested, none detected
Utility contact
Frequently asked questions about Pike County Water Authority
Is Pike County Water Authority tap water safe to drink?
EPA monitoring detected 25 contaminants in Pike County Water Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pike County Water Authority's water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Copper, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Pike County Water Authority serve?
Pike County Water Authority reports serving 12,021 people in Alabama, per its EPA record.
Has Pike County Water Authority had any water quality violations?
The EPA has 220 violations on file for Pike County Water Authority, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.