Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2013-05-01 → 2013-05-31 |
| MCL | Health-based | Resolved | 2013-05-01 → 2013-05-31 |
| MCL | Health-based | Resolved | 2013-05-01 → 2013-05-31 |
| MCL | Health-based | Resolved | 2013-05-01 → 2013-05-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Archived | 1998-07-01 → 1998-07-31 |
| MCL | Health-based | Archived | 1998-07-01 → 1998-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2135 µg/L 21% of the EPA limit 10000 µg/L
worst single sample: 2300 µg/L | 116/140 | SYR4 | 2012–2019 |
| Copper | 464 µg/L 36% of the EPA limit 1300 µg/L
worst single sample: 530 µg/L | 33/56 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 2097 µg/L 21% of the EPA limit 10000 µg/L
worst single sample: 2230 µg/L | 23/26 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17 µg/L 28% of the EPA limit 60 µg/L | 21/34 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| TTHM | 11.915 µg/L 15% of the EPA limit 80 µg/L
worst single sample: 12.2 µg/L | 20/34 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 5.32 pCi/L 35% of the EPA limit 15 pCi/L
worst single sample: 6.6 pCi/L | 17/20 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.167 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 7/48 | SYR4 | 2012–2019 |
| Chloroform | 2.822 µg/L No EPA limit set
worst single sample: 2.96 µg/L | 7/48 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.631 µg/L No EPA limit set
worst single sample: 4 µg/L | 7/48 | SYR4 | 2012–2019 |
| Barium | 60 µg/L 3% of the EPA limit 2000 µg/L
worst single sample: 61 µg/L | 5/26 | SYR4 | 2012–2019 |
| Fluoride | 454 µg/L 11% of the EPA limit 4000 µg/L
worst single sample: 460 µg/L | 5/26 | SYR4 | 2012–2019 |
| Lead | 6.265 µg/L 42% of the EPA limit 15 µg/L
worst single sample: 7 µg/L | 4/56 | SYR4 | 2012–2019 |
| Bromoform | 0.7180 µg/L No EPA limit set
worst single sample: 0.7200 µg/L | 3/48 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.685 pCi/L 34% of the EPA limit 5 pCi/L
worst single sample: 1.7 pCi/L | 2/2 | SYR4 | 2013 |
| Lithium | 9.7 µg/L No EPA limit set | 2/18 | UCMR-5 | 2024 |
| Xylenes, Total | 0.6100 µg/L 0% of the EPA limit 10000 µg/L | 1/48 | SYR4 | 2012–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Pickens County Water Authority
Is Pickens County Water Authority tap water safe to drink?
EPA monitoring detected 17 contaminants in Pickens County Water Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pickens County Water Authority's water?
EPA monitoring detected Nitrate, Copper, Nitrate-Nitrite, Total Haloacetic Acids (HAA5), Lead, and others. The full list with the level and data source for each is above.
How many people does Pickens County Water Authority serve?
Pickens County Water Authority reports serving 14,364 people in Alabama, per its EPA record.
Has Pickens County Water Authority had any water quality violations?
The EPA has 129 violations on file for Pickens County Water Authority, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.