← Alabama

Tap water quality report

Decatur, Municipal Ub of

EPA monitoring tested this supplier for 104 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

104
contaminants tested
13
detected
77,103
people served
1
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Morgan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
7
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2001-10-01 → 2001-12-31
MR Monitoring Resolved 2020-01-01 → 2022-01-31
MR Monitoring Resolved 2020-01-01 → 2022-01-31
MR Monitoring Resolved 2014-03-01 → 2014-03-31
MR Monitoring Resolved 2014-03-01 → 2014-03-31
MR Monitoring Resolved 2014-03-01 → 2014-03-31
MR Monitoring Resolved 2014-03-01 → 2014-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0130 µg/L 3/4 2024
PFBS 0.0034 µg/L 2/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
43 µg/L 54%
of the EPA limit 80 µg/L
worst single sample: 74 µg/L
374/374 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
32.94 µg/L 55%
of the EPA limit 60 µg/L
worst single sample: 54.5 µg/L
374/374 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
35/35 LCR 2024
Copper
297.6 µg/L 23%
of the EPA limit 1300 µg/L
worst single sample: 1850 µg/L
33/41 SYR4 2012–2019
Nitrate
620 µg/L 6.2%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
7.417 µg/L
No EPA limit set
worst single sample: 7.97 µg/L
8/8 SYR4 2012–2019
Chloroform
18.22 µg/L
No EPA limit set
worst single sample: 19.2 µg/L
8/8 SYR4 2012–2019
Fluoride
880 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 950 µg/L
8/8 SYR4 2012–2019
Nitrate-Nitrite
609.5 µg/L 6.1%
of the EPA limit 10000 µg/L
worst single sample: 620 µg/L
8/8 SYR4 2012–2019
Dibromochloromethane
1.7875 µg/L
No EPA limit set
worst single sample: 1.94 µg/L
6/8 SYR4 2012–2019
Lead
19 µg/L 127%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
1/41 SYR4 2012–2019
91 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WILEY, HAGLER
Phone
256-552-1428
Email
[email protected]

Frequently asked questions about Decatur, Municipal Ub of

Is Decatur, Municipal Ub of tap water safe to drink?

EPA monitoring detected 13 contaminants in Decatur, Municipal Ub of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Decatur, Municipal Ub of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Copper, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Decatur, Municipal Ub of serve?

Decatur, Municipal Ub of reports serving 77,103 people in Alabama, per its EPA record.

Has Decatur, Municipal Ub of had any water quality violations?

The EPA has 7 violations on file for Decatur, Municipal Ub of, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?