Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2024-07-01 → 2024-09-30 |
| MR | Monitoring | Resolved | 2024-07-01 → 2024-09-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2022-10-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-10-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-04-01 → 2022-06-30 |
| MR | Monitoring | Resolved | 2022-04-01 → 2022-06-30 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 60.14 µg/L 75% of the EPA limit 80 µg/L
worst single sample: 86.1 µg/L | 133/133 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 48.325 µg/L 81% of the EPA limit 60 µg/L
worst single sample: 64.2 µg/L | 116/133 | SYR4 | 2012–2019 |
| Copper | 75.24 µg/L 5.8% of the EPA limit 1300 µg/L
worst single sample: 114 µg/L | 60/68 | SYR4 | 2012–2019 |
| Nitrate | 3600 µg/L 36% of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L | 52/52 | SYR4 | 2012–2019 |
| Lead | 0.00055 mg/L 3.7% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2025 |
| Chloroform | 22.14 µg/L No EPA limit set
worst single sample: 32 µg/L | 18/19 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 3557.5 µg/L 36% of the EPA limit 10000 µg/L
worst single sample: 3600 µg/L | 18/18 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.714 µg/L No EPA limit set
worst single sample: 8.45 µg/L | 15/19 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.189 µg/L No EPA limit set
worst single sample: 2.42 µg/L | 12/20 | SYR4 | 2012–2019 |
| Barium | 24.98 µg/L 1.2% of the EPA limit 2000 µg/L
worst single sample: 25.4 µg/L | 7/7 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 2.6652 pCi/L 18% of the EPA limit 15 pCi/L
worst single sample: 3.6 pCi/L | 7/8 | SYR4 | 2012–2019 |
| Fluoride | 763.5 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 790 µg/L | 6/7 | SYR4 | 2012–2019 |
| Lead | 6.23 µg/L 42% of the EPA limit 15 µg/L
worst single sample: 7.21 µg/L | 6/68 | SYR4 | 2012–2019 |
| Trichloroethylene | 6.185 µg/L 124% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 6.2 µg/L | 6/20 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.9990 pCi/L 20% of the EPA limit 5 pCi/L
worst single sample: 1.053 pCi/L | 5/7 | SYR4 | 2012–2019 |
| Arsenic | 1.374 µg/L 14% of the EPA limit 10 µg/L
worst single sample: 1.38 µg/L | 3/7 | SYR4 | 2012–2019 |
| Atrazine | 0.1000 µg/L 3.3% of the EPA limit 3 µg/L | 1/10 | SYR4 | 2012–2019 |
| Nitrite | 100 µg/L 10% of the EPA limit 1000 µg/L | 1/18 | SYR4 | 2012–2019 |
| Simazine | 0.0500 µg/L 1.3% of the EPA limit 4 µg/L | 1/10 | SYR4 | 2012–2019 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Madison, the W & Ww Board of the City of
Is Madison, the W & Ww Board of the City of tap water safe to drink?
EPA monitoring detected 21 contaminants in Madison, the W & Ww Board of the City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Madison, the W & Ww Board of the City of's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does Madison, the W & Ww Board of the City of serve?
Madison, the W & Ww Board of the City of reports serving 54,114 people in Alabama, per its EPA record.
Has Madison, the W & Ww Board of the City of had any water quality violations?
The EPA has 227 violations on file for Madison, the W & Ww Board of the City of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.