← Alabama

Tap water quality report

Gordon, Town of

EPA monitoring tested this supplier for 74 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
10
detected
414
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Houston

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
37
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1991-02-01 → 1991-02-28
MCL Health-based Resolved 1991-02-01 → 1991-02-28
MCL Health-based Resolved 1991-02-01 → 1991-02-28
MCL Health-based Resolved 1991-02-01 → 1991-02-28
RPT Monitoring Resolved 2022-04-11
RPT Monitoring Resolved 2022-04-11
Other Monitoring Resolved 2020-10-28
Other Monitoring Resolved 2020-10-28
Other Monitoring Resolved 2020-10-28
Other Monitoring Resolved 2020-10-28

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0118 mg/L 79%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
TTHM
11.88 µg/L 15%
of the EPA limit 80 µg/L
worst single sample: 13.7 µg/L
15/16 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
17.76 µg/L 30%
of the EPA limit 60 µg/L
worst single sample: 18.3 µg/L
13/16 SYR4 2012–2019
Copper
38.45 µg/L 3%
of the EPA limit 1300 µg/L
worst single sample: 61 µg/L
12/15 SYR4 2013–2019
Nitrate
210 µg/L 2.1%
of the EPA limit 10000 µg/L
4/16 SYR4 2012–2019
Bromodichloromethane
1.5135 µg/L
No EPA limit set
worst single sample: 1.56 µg/L
2/2 SYR4 2014–2017
Chloroform
4.923 µg/L
No EPA limit set
worst single sample: 5.14 µg/L
2/2 SYR4 2014–2017
Lead
4.855 µg/L 32%
of the EPA limit 15 µg/L
worst single sample: 5 µg/L
2/15 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
2.72 pCi/L 18%
of the EPA limit 15 pCi/L
1/1 SYR4 2019
Nitrate-Nitrite
180 µg/L 1.8%
of the EPA limit 10000 µg/L
1/3 SYR4 2013–2019
64 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
RAY, SHANNA
Phone
334-522-3113
Email
[email protected]

Frequently asked questions about Gordon, Town of

Is Gordon, Town of tap water safe to drink?

EPA monitoring detected 10 contaminants in Gordon, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Gordon, Town of's water?

EPA monitoring detected Lead, TTHM, Total Haloacetic Acids (HAA5), Copper, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Gordon, Town of serve?

Gordon, Town of reports serving 414 people in Alabama, per its EPA record.

Has Gordon, Town of had any water quality violations?

The EPA has 37 violations on file for Gordon, Town of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.