Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MON | Monitoring | Resolved | 2025-04-01 → 2025-04-30 |
| MON | Monitoring | Resolved | 2025-04-01 → 2025-04-30 |
| MON | Monitoring | Resolved | 2025-04-01 → 2025-04-30 |
| MR | Monitoring | Resolved | 2022-08-07 |
| MR | Monitoring | Resolved | 2022-08-07 |
| MR | Monitoring | Resolved | 2022-08-07 |
| MR | Monitoring | Resolved | 2022-08-07 |
| RPT | Monitoring | Resolved | 2021-07-11 |
| RPT | Monitoring | Resolved | 2021-07-11 |
| RPT | Monitoring | Resolved | 2021-07-11 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5999.55 µg/L 60% of the EPA limit 10000 µg/L
worst single sample: 6210 µg/L | 152/152 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 5967 µg/L 60% of the EPA limit 10000 µg/L
worst single sample: 6210 µg/L | 69/69 | SYR4 | 2012–2019 |
| Lead | 0.0015 mg/L 10% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2024 |
| Total Haloacetic Acids (HAA5) | 1.6009 µg/L 2.7% of the EPA limit 60 µg/L
worst single sample: 1.61 µg/L | 15/16 | SYR4 | 2012–2019 |
| Copper | 102.7 µg/L 7.9% of the EPA limit 1300 µg/L
worst single sample: 208 µg/L | 14/29 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.1380 µg/L 2.3% of the EPA limit 6 µg/L
worst single sample: 0.1600 µg/L | 12/26 | SYR4 | 2012–2019 |
| Barium | 132.6 µg/L 6.6% of the EPA limit 2000 µg/L
worst single sample: 138 µg/L | 7/9 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 4.002 pCi/L 27% of the EPA limit 15 pCi/L
worst single sample: 4.11 pCi/L | 7/7 | SYR4 | 2012–2017 |
| TTHM | 5.21 µg/L 6.5% of the EPA limit 80 µg/L
worst single sample: 5.6 µg/L | 7/16 | SYR4 | 2012–2019 |
| Atrazine | 0.0440 µg/L 1.5% of the EPA limit 3 µg/L
worst single sample: 0.0500 µg/L | 5/20 | SYR4 | 2012–2019 |
| Fluoride | 17.8 µg/L 0.4% of the EPA limit 4000 µg/L
worst single sample: 18 µg/L | 5/9 | SYR4 | 2012–2019 |
| Lead | 13.7 µg/L 91% of the EPA limit 15 µg/L
worst single sample: 14 µg/L | 4/29 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.071 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 3/19 | SYR4 | 2012–2019 |
| Chloroform | 1.202 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 3/19 | SYR4 | 2012–2019 |
| Chromium | 0.6182 µg/L 0.6% of the EPA limit 100 µg/L
worst single sample: 0.6250 µg/L | 3/9 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.7610 µg/L No EPA limit set
worst single sample: 0.7800 µg/L | 3/18 | SYR4 | 2012–2019 |
| Mercury | 0.5283 µg/L 26% of the EPA limit 2 µg/L
worst single sample: 0.5620 µg/L | 3/9 | SYR4 | 2012–2019 |
| Xylenes, Total | 9.46 µg/L 0.1% of the EPA limit 10000 µg/L
worst single sample: 9.5 µg/L | 3/19 | SYR4 | 2012–2019 |
| Ethylbenzene | 1.067 µg/L 0.2% of the EPA limit 700 µg/L
worst single sample: 1.1 µg/L | 2/18 | SYR4 | 2012–2019 |
| Ethylene Dibromide | 0.0400 µg/L 80% of the EPA limit 0.0500 µg/L | 1/24 | SYR4 | 2012–2019 |
| Thallium, Total | 1.23 µg/L 62% of the EPA limit 2 µg/L | 1/9 | SYR4 | 2012–2019 |
76 contaminants tested, none detected
Utility contact
Frequently asked questions about Belforest Water
Is Belforest Water tap water safe to drink?
EPA monitoring detected 28 contaminants in Belforest Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Belforest Water's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Lead, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.
How many people does Belforest Water serve?
Belforest Water reports serving 17,268 people in Alabama, per its EPA record.
Has Belforest Water had any water quality violations?
The EPA has 133 violations on file for Belforest Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.