← Alaska

Tap water quality report

Tatitlek Water

EPA monitoring tested this supplier for 38 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

38
contaminants tested
15
detected
95
people served
287
health-based violations
Water source
Surface water
Ownership
Native American
Counties served
Valdez-Cordova Census Area

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

287
health-based violations
1,236
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2026-01-01 → 2026-03-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Archived 2025-10-01 → 2025-12-31
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0023 mg/L 15%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Chloroform
94 µg/L
No EPA limit set
worst single sample: 97 µg/L
13/13 SYR4 2012–2019
Dichloroacetic Acid
114 µg/L
No EPA limit set
worst single sample: 120 µg/L
13/13 SYR4 2012–2019
TTHM
95.92 µg/L 120%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 98.8 µg/L
13/13 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
308 µg/L 513%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 350 µg/L
13/13 SYR4 2012–2019
Trichloroacetic Acid
194 µg/L
No EPA limit set
worst single sample: 230 µg/L
13/13 SYR4 2012–2019
Bromodichloromethane
3.29 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
12/13 SYR4 2012–2019
Copper
1148 µg/L 88%
of the EPA limit 1300 µg/L
worst single sample: 1400 µg/L
10/10 SYR4 2015–2018
Lead
12.515 µg/L 83%
of the EPA limit 15 µg/L
worst single sample: 15 µg/L
8/10 SYR4 2015–2018
Monochloroacetic Acid
9.717 µg/L
No EPA limit set
worst single sample: 12 µg/L
7/12 SYR4 2012–2019
Nitrate-Nitrite
236.4 µg/L 2.4%
of the EPA limit 10000 µg/L
worst single sample: 240 µg/L
5/7 SYR4 2012–2019
Combined Radium (-226 And -228)
0.4136 pCi/L 8.3%
of the EPA limit 5 pCi/L
worst single sample: 0.4300 pCi/L
2/2 SYR4 2015–2017
Nitrate
453 µg/L 4.5%
of the EPA limit 10000 µg/L
2/2 SYR4 2017
Toluene
1.0055 µg/L 0.1%
of the EPA limit 1000 µg/L
worst single sample: 1.02 µg/L
2/16 SYR4 2012–2019
Xylenes, Total
1.21 µg/L 0%
of the EPA limit 10000 µg/L
1/16 SYR4 2012–2019
23 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneBenzeneBromoformChlorobenzeneCarbon TetrachlorideDichloromethaneDibromoacetic AcidDibromochloromethaneEthylbenzeneMonobromoacetic AcidStyreneTetrachloroethyleneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
STELLWAG, DESERAE
Phone
907-325-2311
Email
[email protected]

Frequently asked questions about Tatitlek Water

Is Tatitlek Water tap water safe to drink?

EPA monitoring detected 15 contaminants in Tatitlek Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Tatitlek Water's water?

EPA monitoring detected Lead, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Tatitlek Water serve?

Tatitlek Water reports serving 95 people in Alaska, per its EPA record.

Has Tatitlek Water had any water quality violations?

The EPA has 1236 violations on file for Tatitlek Water, of which 287 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.