← Alaska

Tap water quality report

Eek Water

EPA monitoring tested this supplier for 100 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
11
detected
280
people served
48
health-based violations
Water source
Surface water
Ownership
Native American
Counties served
Bethel Census Area

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

48
health-based violations
1,299
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2022-08-01 → 2022-08-31
TT Health-based Resolved 2012-01-01 → 2012-01-31
TT Health-based Resolved 2008-12-01 → 2008-12-31
TT Health-based Resolved 2006-11-01 → 2006-11-30
TT Health-based Resolved 2006-11-01 → 2006-11-30
TT Health-based Resolved 2003-12-01 → 2003-12-31
TT Health-based Resolved 2003-12-01 → 2003-12-31
TT Health-based Resolved 2003-04-01 → 2003-04-30
TT Health-based Resolved 2003-04-01 → 2003-04-30
TT Health-based Resolved 2003-03-01 → 2003-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0054 mg/L 36%
of the EPA limit 0.0150 mg/L
14/14 LCR 2026
Copper
1150 µg/L 88%
of the EPA limit 1300 µg/L
worst single sample: 1200 µg/L
11/11 SYR4 2012–2016
Lead
22 µg/L 147%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 27 µg/L
11/11 SYR4 2012–2016
Bromodichloromethane
3.24 µg/L
No EPA limit set
worst single sample: 3.3 µg/L
6/6 SYR4 2012–2018
Chloroform
42.7 µg/L
No EPA limit set
worst single sample: 44 µg/L
6/6 SYR4 2012–2018
TTHM
45.35 µg/L 57%
of the EPA limit 80 µg/L
worst single sample: 46.5 µg/L
6/6 SYR4 2012–2018
Nitrate-Nitrite
106 µg/L 1.1%
of the EPA limit 10000 µg/L
4/12 SYR4 2012–2018
Dichloroacetic Acid
1.19 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
2/6 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
10.59 µg/L 18%
of the EPA limit 60 µg/L
worst single sample: 11 µg/L
2/6 SYR4 2012–2018
Trichloroacetic Acid
9.485 µg/L
No EPA limit set
worst single sample: 9.9 µg/L
2/6 SYR4 2012–2018
Antimony, Total
0.1080 µg/L 1.8%
of the EPA limit 6 µg/L
1/1 SYR4 2012
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PETLUSKA, FRITZ
Phone
907-536-5129
Email
[email protected]

Frequently asked questions about Eek Water

Is Eek Water tap water safe to drink?

EPA monitoring detected 11 contaminants in Eek Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Eek Water's water?

EPA monitoring detected Lead, Copper, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Eek Water serve?

Eek Water reports serving 280 people in Alaska, per its EPA record.

Has Eek Water had any water quality violations?

The EPA has 1299 violations on file for Eek Water, of which 48 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.