Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2004-01-01 → 2004-01-31 |
| TT | Health-based | Resolved | 2003-03-01 → 2003-03-31 |
| TT | Health-based | Resolved | 2003-01-01 → 2003-01-31 |
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2025-10-01 → 2025-12-31 |
| MON | Monitoring | Resolved | 2024-05-01 → 2024-05-31 |
| MR | Monitoring | Resolved | 2024-05-01 → 2024-05-31 |
| MR | Monitoring | Resolved | 2024-05-01 → 2024-05-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1189 µg/L 91% of the EPA limit 1300 µg/L
worst single sample: 2700 µg/L | 60/60 | SYR4 | 2012–2018 |
| Lead | 24.4 µg/L 163% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 71.7 µg/L | 51/60 | SYR4 | 2012–2018 |
| Bromodichloromethane | 9.33 µg/L No EPA limit set
worst single sample: 11.8 µg/L | 43/45 | SYR4 | 2012–2019 |
| Chloroform | 28.61 µg/L No EPA limit set
worst single sample: 29 µg/L | 43/45 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.509 µg/L No EPA limit set
worst single sample: 4.74 µg/L | 43/45 | SYR4 | 2012–2019 |
| TTHM | 40 µg/L 50% of the EPA limit 80 µg/L
worst single sample: 40.8 µg/L | 41/45 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 17 µg/L No EPA limit set
worst single sample: 20 µg/L | 40/45 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 36.295 µg/L 60% of the EPA limit 60 µg/L
worst single sample: 42 µg/L | 40/45 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 21.05 µg/L No EPA limit set
worst single sample: 23 µg/L | 40/45 | SYR4 | 2012–2019 |
| Lead | 0.0031 mg/L 20% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2024 |
| Nitrate-Nitrite | 140 µg/L 1.4% of the EPA limit 10000 µg/L | 8/48 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.275 µg/L No EPA limit set
worst single sample: 1.34 µg/L | 6/45 | SYR4 | 2012–2019 |
| Arsenic | 2.575 µg/L 26% of the EPA limit 10 µg/L
worst single sample: 2.66 µg/L | 3/6 | SYR4 | 2012–2018 |
| Combined Uranium | 0.3486 µg/L 1.2% of the EPA limit 30 µg/L
worst single sample: 0.3520 µg/L | 2/2 | SYR4 | 2013 |
| Barium | 6.7 µg/L 0.3% of the EPA limit 2000 µg/L | 1/3 | SYR4 | 2015 |
| Bromoform | 0.5090 µg/L No EPA limit set | 1/45 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 21 µg/L No EPA limit set | 1/45 | SYR4 | 2012–2019 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Unalaska Water
Is Unalaska Water tap water safe to drink?
EPA monitoring detected 17 contaminants in Unalaska Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Unalaska Water's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Unalaska Water serve?
Unalaska Water reports serving 9,400 people in Alaska, per its EPA record.
Has Unalaska Water had any water quality violations?
The EPA has 300 violations on file for Unalaska Water, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.