Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2015-06-01 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MCL | Health-based | Resolved | 2014-01-01 → 2014-01-31 |
| MON | Monitoring | Resolved | 2025-05-01 → 2025-05-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFHXS | 0.0042 µg/L | 2/10 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 662.25 µg/L 51% of the EPA limit 1300 µg/L
worst single sample: 1500 µg/L | 158/158 | SYR4 | 2018–2019 |
| TTHM | 19.26 µg/L 24% of the EPA limit 80 µg/L
worst single sample: 52.9 µg/L | 109/109 | SYR4 | 2012–2019 |
| Chloroform | 15.915 µg/L No EPA limit set
worst single sample: 42.5 µg/L | 108/109 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.535 µg/L No EPA limit set
worst single sample: 10.4 µg/L | 106/109 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 11 µg/L 18% of the EPA limit 60 µg/L
worst single sample: 16.2 µg/L | 100/108 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 5.1475 µg/L No EPA limit set
worst single sample: 10 µg/L | 96/108 | SYR4 | 2012–2019 |
| Lead | 9.16 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 500 µg/L | 85/158 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 5.7 µg/L No EPA limit set
worst single sample: 8.68 µg/L | 76/108 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.355 µg/L No EPA limit set
worst single sample: 2.77 µg/L | 70/109 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1250 µg/L 13% of the EPA limit 10000 µg/L
worst single sample: 1370 µg/L | 50/86 | SYR4 | 2012–2019 |
| Arsenic | 12.98 µg/L 130% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 21 µg/L | 49/51 | SYR4 | 2013–2019 |
| Lead | 0.0031 mg/L 21% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2024 |
| Barium | 33.4 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 39 µg/L | 8/8 | SYR4 | 2013–2019 |
| Bromoform | 0.6960 µg/L No EPA limit set
worst single sample: 0.7200 µg/L | 5/109 | SYR4 | 2012–2019 |
| Toluene | 0.7940 µg/L 0.1% of the EPA limit 1000 µg/L
worst single sample: 0.8000 µg/L | 3/21 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.095 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/107 | SYR4 | 2012–2019 |
| Xylenes, Total | 6.4315 µg/L 0.1% of the EPA limit 10000 µg/L
worst single sample: 6.72 µg/L | 2/21 | SYR4 | 2012–2019 |
| Cyanide | 4.6 µg/L 2.3% of the EPA limit 200 µg/L | 1/5 | SYR4 | 2013–2019 |
| Cadmium | 0.1510 µg/L 3% of the EPA limit 5 µg/L | 1/8 | SYR4 | 2013–2019 |
| Chromium | 0.6630 µg/L 0.7% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2013–2019 |
| Ethylbenzene | 0.8800 µg/L 0.1% of the EPA limit 700 µg/L | 1/21 | SYR4 | 2012–2019 |
| Fluoride | 113 µg/L 2.8% of the EPA limit 4000 µg/L | 1/5 | SYR4 | 2013–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Wasilla Water
Is Wasilla Water tap water safe to drink?
EPA monitoring detected 23 contaminants in Wasilla Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wasilla Water's water?
EPA monitoring detected Copper, TTHM, Chloroform, Bromodichloromethane, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Wasilla Water serve?
Wasilla Water reports serving 18,492 people in Alaska, per its EPA record.
Has Wasilla Water had any water quality violations?
The EPA has 178 violations on file for Wasilla Water, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.