← Oregon

Tap water quality report

Warm Springs Water Treatment Plant

EPA monitoring tested this supplier for 112 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
15
detected
3,800
people served
58
health-based violations
Water source
Surface water
Ownership
Native American

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

58
health-based violations
455
violations on file
23
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2025-07-08
TT Health-based Unaddressed 2024-10-17
TT Health-based Resolved 2019-04-01 → 2019-04-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
72.05 µg/L 5.5%
of the EPA limit 1300 µg/L
worst single sample: 115 µg/L
38/60 SYR4 2013–2019
Chloroform
34.7 µg/L
No EPA limit set
worst single sample: 57.7 µg/L
31/31 SYR4 2012–2019
Bromodichloromethane
5.255 µg/L
No EPA limit set
worst single sample: 5.8 µg/L
30/31 SYR4 2012–2019
TTHM
41.165 µg/L 51%
of the EPA limit 80 µg/L
worst single sample: 62.9 µg/L
30/30 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
39.995 µg/L 67%
of the EPA limit 60 µg/L
worst single sample: 51.9 µg/L
24/30 SYR4 2012–2019
Trichloroacetic Acid
24.995 µg/L
No EPA limit set
worst single sample: 36.5 µg/L
24/30 SYR4 2012–2019
Dibromochloromethane
1.12 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
19/31 SYR4 2012–2019
Dichloroacetic Acid
17.2 µg/L
No EPA limit set
19/30 SYR4 2012–2019
Lead
0.0140 mg/L 93%
of the EPA limit 0.0150 mg/L
7/7 LCR 2021
Lead
14 µg/L 93%
of the EPA limit 15 µg/L
worst single sample: 16 µg/L
5/61 SYR4 2012–2019
Dibromoacetic Acid
1.38 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
3/30 SYR4 2012–2019
Combined Radium (-226 And -228)
1.4737 pCi/L 29%
of the EPA limit 5 pCi/L
worst single sample: 1.5 pCi/L
2/3 SYR4 2013–2018
Monobromoacetic Acid
1.2 µg/L
No EPA limit set
2/30 SYR4 2012–2019
Fluoride
202 µg/L 5.1%
of the EPA limit 4000 µg/L
1/1 SYR4 2012
Monochloroacetic Acid
2.8 µg/L
No EPA limit set
1/30 SYR4 2012–2019
97 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitrateNitrate-NitriteNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PALMER, RONALD
Phone
541-553-1472
Email
[email protected]

Frequently asked questions about Warm Springs Water Treatment Plant

Is Warm Springs Water Treatment Plant tap water safe to drink?

EPA monitoring detected 15 contaminants in Warm Springs Water Treatment Plant's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Warm Springs Water Treatment Plant's water?

EPA monitoring detected Copper, Chloroform, Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Warm Springs Water Treatment Plant serve?

Warm Springs Water Treatment Plant reports serving 3,800 people in Oregon, per its EPA record.

Has Warm Springs Water Treatment Plant had any water quality violations?

The EPA has 455 violations on file for Warm Springs Water Treatment Plant, of which 58 are health-based (a contaminant limit or required treatment was breached) and 23 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.