← North Carolina

Tap water quality report

Mocksville, NC

EPA monitoring detected 22 contaminants across the 3 water suppliers serving Mocksville. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

3
water suppliers
37,822
people served
22
contaminants found

What was found in Mocksville's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
1440 µg/L 14%
of the EPA limit 10000 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
Highest in the city: 4300 µg/L — SHEFFIELD PARK S/D · 79 people · 2019
3/3 SYR4
Nitrate-Nitrite
1411.5 µg/L 14%
of the EPA limit 10000 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
Highest in the city: 4300 µg/L — SHEFFIELD PARK S/D · 79 people · 2015
3/3 SYR4
Fluoride
760 µg/L 19%
of the EPA limit 4000 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
3/3 SYR4
Copper
139.2 µg/L 11%
of the EPA limit 1300 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2018
Highest in the city: 364.05 µg/L — SHEFFIELD PARK S/D · 79 people · 2019
3/3 SYR4
Chloroform
79.05 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
TTHM
77.34 µg/L 97%
of the EPA limit 80 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
Total Haloacetic Acids (HAA5)
42.85 µg/L 71%
of the EPA limit 60 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
Highest in the city: 48.975 µg/L — MOCKSVILLE, TOWN OF · 6,200 people · 2019
2/3 SYR4
Lead
48.75 µg/L 325%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
Highest in the city: MOCKSVILLE, TOWN OF · 6,200 people · 2017
2/3 SYR4
Trichloroacetic Acid
18 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
Highest in the city: 30.36 µg/L — MOCKSVILLE, TOWN OF · 6,200 people · 2019
2/3 SYR4
Dichloroacetic Acid
26 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
Bromodichloromethane
9.905 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
Highest in the city: 11.275 µg/L — MOCKSVILLE, TOWN OF · 6,200 people · 2019
2/3 SYR4
Monobromoacetic Acid
4 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
Monochloroacetic Acid
3.83 µg/L
No EPA limit set
Highest in the city: MOCKSVILLE, TOWN OF · 6,200 people · 2019
1/3 SYR4
Xylenes, Total
3 µg/L 0%
of the EPA limit 10000 µg/L
Highest in the city: SHEFFIELD PARK S/D · 79 people · 2018
1/3 SYR4
Dibromochloromethane
1.9 µg/L
No EPA limit set
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
Dibromoacetic Acid
1.4 µg/L
No EPA limit set
Highest in the city: MOCKSVILLE, TOWN OF · 6,200 people · 2019
1/3 SYR4
Ethylbenzene
0.6300 µg/L 0.1%
of the EPA limit 700 µg/L
Highest in the city: SHEFFIELD PARK S/D · 79 people · 2018
1/3 SYR4
Combined Radium (-226 And -228)
0.3950 pCi/L 7.9%
of the EPA limit 5 pCi/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2017
Highest in the city: 0.6000 pCi/L — MOCKSVILLE, TOWN OF · 6,200 people · 2013
2/3 SYR4
Simazine
0.1800 µg/L 4.5%
of the EPA limit 4 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
1/3 SYR4
Atrazine
0.1300 µg/L 4.3%
of the EPA limit 3 µg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2019
2/3 SYR4
6:2 Fts
0.0123 µg/L
No EPA limit set
Highest in the city: MOCKSVILLE, TOWN OF · 6,200 people · 2023
1/3 UCMR-5
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
Main supplier: DAVIE COUNTY WATER SYSTEM · 31,543 people · 2025
Highest in the city: 0.0019 mg/L — SHEFFIELD PARK S/D · 79 people · 2025
3/3 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Mocksville

SupplierPopulation served
DAVIE COUNTY WATER SYSTEM 31,543
MOCKSVILLE, TOWN OF 6,200
SHEFFIELD PARK S/D 79

Frequently asked questions about Mocksville tap water

Is Mocksville tap water safe to drink?

EPA testing detected 22 contaminants in the water serving Mocksville. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Mocksville?

3 public water suppliers report drinking-water monitoring for Mocksville, North Carolina to the EPA. Each is listed above with its population served.

What contaminants are in Mocksville's water?

The contaminants EPA monitoring detected in Mocksville include Nitrate, Nitrate-Nitrite, Fluoride, Copper, Chloroform. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.