What was found in Council Grove's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Fluoride | 970.5 µg/L 24% of the EPA limit 4000 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Nitrate | 488.5 µg/L 4.9% of the EPA limit 10000 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Barium | 79.3 µg/L 4% of the EPA limit 2000 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| TTHM | 57.4 µg/L 72% of the EPA limit 80 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Copper | 56.25 µg/L 4.3% of the EPA limit 1300 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Chloroform | 36.5 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Total Haloacetic Acids (HAA5) | 20 µg/L 33% of the EPA limit 60 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Bromodichloromethane | 11.5 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Trichloroacetic Acid | 10.16 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Bromate | 8.89 µg/L 89% of the EPA limit 10 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Dichloroacetic Acid | 8.04 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Monochloroacetic Acid | 7.36 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Dibromochloromethane | 4.7 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Dibromoacetic Acid | 2.485 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Lead | 2.42 µg/L 16% of the EPA limit 15 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Chromium | 1.775 µg/L 1.8% of the EPA limit 100 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Selenium | 1.59 µg/L 3.2% of the EPA limit 50 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Combined Radium (-226 And -228) | 1.3 pCi/L 26% of the EPA limit 5 pCi/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2017 | 1/2 | SYR4 |
| Monobromoacetic Acid | 1.3 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Arsenic | 1.185 µg/L 12% of the EPA limit 10 µg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Bromoform | 0.6420 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2019 | 1/2 | SYR4 |
| Pfba | 0.0069 µg/L No EPA limit set Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2023 | 1/2 | UCMR-5 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L Main supplier: COUNCIL GROVE, CITY OF · 2,111 people · 2023 | 2/2 | LCR |
Water suppliers serving Council Grove
| Supplier | Population served |
|---|---|
| COUNCIL GROVE, CITY OF | 2,111 |
| MORRIS CO RWD 2 | 25 |
Frequently asked questions about Council Grove tap water
Is Council Grove tap water safe to drink?
EPA testing detected 23 contaminants in the water serving Council Grove. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Council Grove?
2 public water suppliers report drinking-water monitoring for Council Grove, Kansas to the EPA. Each is listed above with its population served.
What contaminants are in Council Grove's water?
The contaminants EPA monitoring detected in Council Grove include Fluoride, Nitrate, Barium, TTHM, Copper. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.